Operation: The glass bulb contains a
fluid which expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently to
shatter the glass bulb, which then
allows the sprinkler to activate & flow
water.

WARNING

The Model WS Specific Application
Window Sprinklers described herein
must be installed & maintained in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association, in
addition to the standards of any other
authorities having jurisdiction. Failure to
do so may impair the integrity of these
devices.

The owner is responsible for
maintaining their fire protection system
and devices in proper operating
condition. The installing contractor or
sprinkler manufacturer should be
contacted relative to any questions.

Sprinkler Identification Number
SIN C3388 - Horizontal Sidewall
SIN C3488 - Pendent Vertical Sidewall

Approvals
UL, C-UL & ULC Listed. NYC Approved.
(The approvals apply only to the service
conditions indicated in the Design
Criteria Section)

Additional Recognition:
National Evaluation Service (NER 516)
ICBO Evaluation Service (ER 5790)

Pipe Thread Connection
1/2 inch NPT

Discharge Coefficient
K = 5.6 GPM/psi

1/2

 (80.6 LPM/bar

1/2

)

Temperature Ratings
155

°

F/68

°

C & 200

°

F/93

°

C

Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass

Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model WS

TM

Specific Application
Window Sprinklers™

5.6 K-factor - Quick Response

Vertical Sidewall & Horiz. Sidewall Glass Bulb Automatic Sprinkler

No. 6-2.0

General
Description

The Central Model WS, 5.6 K-factor,
Pendent Vertical Sidewall and Horizon-
tal Sidewall, Specific Application
Window Sprinklers are quick response
glass bulb type spray sprinklers.

These sprinklers are the first sprinklers
ever to be specifically Listed to provide
protection for heat strengthened or
tempered glass windows using closed
sprinklers.  As part of the testing, the
gas flow required to achieve the time/
temperature relationship specified in
ASTM E119 was established in a test
furnace without sprinkler protection.  A
Window assembly protected with Model
WS Specific Application Window
Sprinklers was then installed in the test
furnace and the same gas flow condi-
tions were maintained for a two hour
test period.  No cracking or visible
damage to the window was permitted
during the test period (even when a
hose stream was directed at the window).

The success of the Model WS Specific
Application Window Sprinkler is based
on its specially designed deflector, that
ensures that the spray pattern wets the
entire surface of the window, and its
fast response thermal sensitivity.

Based on this successful testing, the
Model WS Specific Application Window
Sprinkler can be used as interior
protection of windows or glazing in a
sprinklered building or non sprinklered
building.  Also, the Model WS Specific
Application Window Sprinkler can be used
as a open sprinkler for "Outside Sprinkler
Protection against Exposure Fire", using
the design requirements of NFPA.

As with any specific application
sprinkler, the installation instructions
included in this data sheet must be
preciseley followed.  National Evalua-
tion Service Inc. (NES), ICBO Evalua-
tion Service, Inc. (ICBO ES), and
Underwriters Labratories of Canada
(ULC) guidelines apply, consult the
specific approval report.

Technical
Data

CENTRAL

WS

3-01

Specific
Application
Window
Sprinklers

I M

A

O

P

T

Physical Characteristics
The Model WS Window Sprinklers
utilize a dezincification resistant (DZR)
bronze frame and a 3 mm bulb. The
two-piece button assembly is brass
and copper. The sprinkler frame
orifice is sealed with a  gasketed
spring plate (Belleville Seal) consist-
ing of a beryllium nickel disc spring
that is sealed on both its inside and
outside edges with a Teflon

TM

 gasket.

The compression screw is bronze, &
the deflector is brass.

OBSOLETE

Содержание CENTRAL WS

Страница 1: ...are the first sprinklers ever to be specifically Listed to provide protection for heat strengthened or tempered glass windows using closed sprinklers As part of the testing the gas flow required to ac...

Страница 2: ...um Distance from Vertical Mullion 4 101 6 mm Ref Figure D Intermediate Horizontal Mullions Intermediate Horizontal Mullions were not tested with the window sprinkler Their use is outside the scope of...

Страница 3: ...Figure 2 Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler Figure 3 Cross Section Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler 1 5 8 41 3 mm 2 1 8 54...

Страница 4: ...21 ft lbs 28 5 Nm of torque is to be used to install 1 2 inch NPT sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leakage or impair ment of the sprinkler Step 1 The...

Страница 5: ...x 4 1 22 m Min 4 101 6 mm Butt Joint No Minimum or Maximum Mullion Window Sprinklers are NOT required to be located with respect to horizontal or vertical butt joints 8 2 44 m Maximum 6 1 83 m Minimum...

Страница 6: ...e shipped or stored where their tem peratures will exceed 100 F 38 C and they must never be painted plated coated or otherwise altered after leaving the factory Modified sprinklers must be replaced Sp...

Страница 7: ...dified or repaired in accordance with applicable Standards of the National Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found by Tyco Fire Pr...

Страница 8: ...Products Figure H Recessed Ceiling Condition Pendent Vertical and Horizontal Sidewall Window Sprinklers can be installed into recessed ceiling spaces Curtains blinds or other window coverings are NOT...

Отзывы: