Optima™, Omega™ & Glass Bulb Residential Sprinkler

Design and Installation Guide

Figure  9

Obstruction to Discharge by Inter-

secting Flat Ceiling

If “D” is “Obstructed” per Figure 9 Graph, then “D” is to be
considered the area of coverage and additional sprinklers
along the horizontal ceiling will be necessary.  Only if “D” is
“Acceptable” can “A” be considered 

1

2

 of the maximum

Listed spacing that the sprinkler was calculated for.  Di-
mension “A” is measured along the slope.

D

F

A

A — Maximum 

1

2

 of the Listed spacing that the sprinkler

was calculated for.

D — Distance to intersecting horizontal ceiling.

F — Acceptable for angles 0

°

 to 60

°

.

Figure 9 Graph

0

°

     4

°

     8

°

     12

°

   16

°

    20

°

 

   24

°

    28

°

     32

°

   36

°

   40

°

  44

°

   48

°

   52

°

   56

°

   60

°

"D"

(in feet)

"F"

(in degrees)

Obstructed

Acceptable

10'

9'

8'

6'

5'

4'

3'

2'

7'

20' x 20'

18' x 18'

16' x 16'

14' x 14'

12' x 12'

Figure  10

Obstruction to Discharge by an Oppos-

ing Sloped Ceiling

If “D” is “Obstructed” per Figure 10 Graph, then the hori-
zontal distance to the opposing slope is the extent of
coverage and additional sprinklers will be necessary to
protect the remainder of the opposing slope.  Only if “D” is
“Acceptable” can “A” equal 

1

2

 of the maximum Listed

spacing that the sprinkler was calculated for.  Dimension
“A” is measured along the slope.

A

D

A

G

F

A — NFPA minimum of 4", maximum 

1

2

 of the Listed

spacing that the sprinkler was calculated for.

D — Distance to opposing sloped ceiling.

F & G — Acceptable for angles 0

°

 to 60

°

.

5'

4'

3'

2'

1'

"D"

(in feet)

"F" or "G" 

(whichever is greater)

(in degrees)

Obstructed

10

°

   15

°

   20

°

    25

°

    30

°

    35

°

    40

°

   45

°

Acceptable

20' x 20'

18' x 18'

16' x 16'

14' x 14'

12' x 12'

Figure  10 Graph

OBSOLETE

Содержание CENTRAL Omega

Страница 1: ...ated more than 3 0 measured vertically from any peaked ceiling C Cold Solder The minimum distance between Residential Sprinklers per NFPA 13D is 8 0 This requirement is based on smooth flat ceiling co...

Страница 2: ...on for sidewall sprinklers Step 2 Use only a non hardening pipe joint compound or Teflon tape Apply only to the male threads Step 3 Hand tighten the sprinkler into the fitting Use the appropriate Cent...

Страница 3: ...14 or less 7 or less 14 10 6 11 6 5 Pendent 16 8 16 13 8 12 7 8 18 9 19 19 5 14 10 6 GBR 7 16 4 3 14 or less 7 or less 14 10 6 11 6 5 Recessed Pendent 16 8 16 13 8 12 7 8 18 9 19 19 5 16 13 8 GBR 7 16...

Страница 4: ...7 34 31 29 27 25 23 22 21 19 18 18 17 5 79 68 59 51 45 40 36 32 29 27 24 23 21 20 18 17 16 16 15 14 4 76 63 63 45 39 34 30 27 24 22 20 18 17 16 15 14 13 13 12 11 3 72 56 45 37 31 27 23 21 18 17 15 14...

Страница 5: ...ated for C Maximum of 3 0 vertically from the peak F Acceptable for angles 0 to 60 G Minimum of 4 for maximum refer to A and measure along slope The minimum distance between sprinklers on opposing slo...

Страница 6: ...0 when minimum of 8 0 cannot be obtained due to B a baffle must be installed between these sprinklers to obstruct the discharge and prevent cold solder See B for maximum F Acceptable for angles 0 to 6...

Страница 7: ...he minimum distance between sprinklers is measured horizontally Staggering sprinklers will help maintain maximum horizontal distances in difficult situations Dimension B is measured along the slope Fo...

Страница 8: ...peak D Refer to Figure 8 F Acceptable for angles 0 to 60 A D C A Figure 8 Obstruction to Discharge by Intersect ing Sloped Ceiling If D is Obstructed per Figure 8 Graph then D is to be considered the...

Страница 9: ...0 D in feet F in degrees Obstructed Acceptable 10 9 8 6 5 4 3 2 7 20 x 20 18 x 18 16 x 16 14 x 14 12 x 12 Figure 10 Obstruction to Discharge by an Oppos ing Sloped Ceiling If D is Obstructed per Figur...

Страница 10: ...s to Heat Sources Sprinklers installed too close to heat sources can operate prematurely and so must be placed a sufficient distance away from the heat source Common heat sources in residential occupa...

Страница 11: ...aced at least 3 6 ordinary temp 1 0 intermediate temp laterally from the surfaces of a stove Sprinklers must be spaced at least 1 6 ordinary temp 0 9 intermediate temp laterally from the surfaces of k...

Страница 12: ...Sprinkler Guide Figure Side of open or Recessed Fireplace 36 12 Figure 14 15 Front of Recessed Fireplace 84 36 Figure 15 Coal or Wood Burning Stove 42 12 Figure 17 Kitchen Range 18 9 Figure 18 Wall Ov...

Отзывы: