background image

10

Table 1* — Spacing for Vertical Obstructions

Figure 13

BB and HIP Sprinklers for Attics Greater

Than 60'

(18,3m)

 and Equal or Less Than

80'

(24,4m)

Figure 14

If the attic has noncombustible insulation on the ceiling

below the attic sprinklers, the area of coverage is

measured from the top of the insulation.

Figure 15 — BB and HIP Sprinklers Plan View Perimeter Protection

Coverage by standard sprinklers

Max. 7' (2,13 m) on center

4 m)

6' (1,83 m)

o.c.

Plan View Parimeter Protection

60'

(18,23 m)

Start spacing

at 31' (9,45 m)

away from corner

10' 

(3,05 m)

10' 

(3,05 m)

Attic sprinklers in buildings over

60'-0"

(18,3m)

 up to 80'-0"

(24,4m)

 wide

Attic sprinklers in conjunction with standard sprinklers
can be used to protect attics over 60'-0"

(18,3m)

 up to

80'-0"

(24,4m)

 wide.  Attics over 80'-0"

(24,4m)

 wide must

use standard sprinklers throughout as attic sprinklers
have not completed testing in this scenario.  To use
attic sprinklers in these attics, space attic sprinklers to
protect the center portion of the building, add standard
sprinklers around the perimeter at a maximum of 7'-0"

(2,1m)

 and a minimum of 6'-0" 

(1,8m)

 on center.  The

HIP™ sprinklers can continue down the hip.  Start
spacing standard sprinklers 31'-0" 

(9,4m)

 away from the

corner.

Standard spray sprinkler

spaced 7'-0" (2,1 m) to

6'-0" (1,8 m)

on center

10' (3,05m)

Max.

60' (18,3 m) maximum for

Attic Sprinkler coverage

 80' (24,4 m)

Attic Sprinklers

Standard spray sprinkler

spaced 7'-0" (2,1 m) to

6'-0" (1,8 m)

on center

10' (3,05m)

Max.

Width of Attic Sprinkler Spacing

 Maximum Dimension

Minimum Horizontal

of Obstruction

Distance to Obstruction

1

2

"-1"

(12,7mm-25,4mm)

6"

(152 mm)

>1"-4"

(25,4mm-101,6mm)

12"

(305 mm)

>4"-8"

(101,6mm-203,2mm)

24"

(610 mm)

>8"-10"

(203,6mm-254mm)

5'

(1,5 m)

>10"-20"

(254mm-508mm)

10'

(3,0 m)

>20"-30"

(508mm-762mm)

15'

(4,6 m)

>30"-40"

(762mm-1016mm)

20'

(6,1 m)

>40"-48"

(1016mm-1219,2mm)

25'

(7,6 m)

>48"

(1219,2mm)

sprinkler required beyond

* When minimum horizontal distance is less than Table 1,

an additional sprinkler is required beyond the obstruction.

OBSOLETE

Содержание CENTRAL Attic

Страница 1: ...the 60 second requirement to be met without an accelerator The other cost reduction is in the new Listing of BlazeMaster CPVC for Attic spaces feeding the wet system sprinklers below the ceiling Tradi...

Страница 2: ...monel thermal sensitive link The sprinkler frame orifice is sealed with a gasketed spring plate Belleville Seal consisting of a beryllium nickel disc spring that is sealed on both its inside and outs...

Страница 3: ...N VIEW 2 50 8 mm 1 2 NPT WRENCH FLAT ELEVATION VIEW Back to Back Dual Directional Attic Sprinkler BB1 17 32 BB2 17 32 BB3 17 32 Back to Back Dual Directional Attic Sprinkler BB1 BB2 BB3 HIP Sprinkler...

Страница 4: ...area above must be protected by Attic Sprinklers see figure 10 Insulation is for fire protection purposes It is not freeze protection BlazeMaster CPVC must be installed in accordance with the BlazeMas...

Страница 5: ...5mm than 10 3 0 m SD2 30 9 1 m to more 25 95 20 0 1 4 7 12 178mm 305mm to less than 10 12 254 mm 305mm than 10 3 0 m SD3 30 9 1 m to more 25 95 20 0 1 4 10 12 254mm 305mm to 12 12 305mm 305mm than 10...

Страница 6: ...kler Single Directional Attic Sprinkler Single Directional Attic Sprinkler Span Dimension Single Directional 16 406 4 mm minimum 22 558 8 mm maximum To Bottom of Sheathing Branch Line Ceiling Truss Ri...

Страница 7: ...the maximum spacing is 6 0 1 8 m and the minimum is 4 0 1 2 m see figures 2 11 The reason 400 square feet is not an issue with the single directional is because at its maximum spacing 6 0 1 8 m on cen...

Страница 8: ...ee figure 12 for joists perpendicular to outside wall Ridge Single Directional Attic Sprinkler Outside Wall 40 0 12 2 m maximum 3 0 0 9 m max on slope Back to Back Attic Sprinkler 6 0 1 8 m Max 6 0 1...

Страница 9: ...be 6 152 4mm clearance over the top of the obstruction to allow water to pass both over and under the obstruction The 6 152 4mm is measured perpendicular to the slope from the bottom of the joist If t...

Страница 10: ...rio To use attic sprinklers in these attics space attic sprinklers to protect the center portion of the building add standard sprinklers around the perimeter at a maximum of 7 0 2 1m and a minimum of...

Страница 11: ...tics having a mixture of standard spray sprinklers and Specific Application Attic SprinklersTM The design area requirements of NFPA 13 shall apply to all sprinkler types 5 Attics having a Width Greate...

Страница 12: ...ith the appli cable standards of the National Fire Protection Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The installing contractor or sprinkler m...

Отзывы: