background image

7

Design Guidelines

To design a project with attic sprinklers use these steps as a
guideline:

•  Determine if single, dual directional or hip sprinkler is needed.
•  Determine the roof slope is between 4:12 to 12:12.  If more than

one slope is being used on a project, select the correct sprinkler
for each area.

•  Follow the guidelines for each type of sprinkler as follows:

For Back to Back 

(dual directional)

•  Determine the throw needed 

(see spacing requirements on

page 5).  If over 20'-0"

(6,1 m)

 up to 60'-0"

(18,3 m)

 is required,

use the 8.0 K-factor back to back dual directional to reduce the
pressure required, or if pressure is not a concern, use the 5.6 K-
factor Sprinklers to minimize over discharge.

•  If less than 20'-0"

(6,1 m)

 is required, use the 5.6 K-factor back to

back dual directional to minimize pressure and flow require-
ments.

•  Determine the distance along the slope.  If the distance is not

equal, use the longer side.  Multiply the longer side by two to
determine the spacing down the slope.  Four hundred divided
by this value will determine the maximum spacing along the
ridge.  The maximum is distance is 6'-0" 

(1,8 m)

.  For example,

a 12:12 slope at the maximum span of 60 feet 

(18,3 m)

 will

produce a slope length of approximately 42.5 feet 

(13,0 m)

.

That number multiplied by two produces a 85'

(25,9 m)

 throw.

Four hundred square feet maximum divided by an 85'

(25,9 m)

throw only allows a 4'-8"

(1,4 m)

 spacing along the ridge.  Using

the maximum spacing, space the sprinklers along the ridge.

•  Avoid obstructions as shown on page 9.  If necessary, add

standard sprinklers to maintain coverage around obstructions.

•  Calculate the sprinkler system in accordance with the

appropriate flow and pressure information on page 5.  There is
no interpolation of the flows and pressures shown on the chart.

For Single Directional
•  Determine the throw needed.
•  As the 400 square feet 

(37,2 m

2

)

 is not a factor with the Single

Directional, the maximum spacing is 6'-0"

(1,8 m)

 and the

minimum is 4'-0"

(1,2 m)

 

(see figures 2 &11).  (The reason 400

square feet is not an issue with the single directional is because
at its maximum spacing, 6'-0" 

(1,8 m)

on center/covering 40'-0"

(12,2 m)

flat / a 12:12 slope / and the throw being 56.5 feet 

(17,2

m)

, the 400 square foot 

(37,2 m

2

)

 maximum would not be

exceeded.)

•  Avoid obstructions as shown on page 9.  If necessary, add

standard sprinklers to maintain coverage around obstructions.

•  Calculate the sprinkler system in accordance with the

appropriate flow and pressure information on page 5.  There is
no interpolation of the flows and pressures shown on the chart.

For HIP Sprinkler 

(see figure 11)

•  Verify framing direction is perpendicular to outside wall 

(see

figures 11 & 12).  If not, cover that area with standard sprinklers.

•  From the intersection of the top of the hip and the ridge the

maximum distance down the slope of the hip is 3'-0"

(0,9 m)

.

Start the layout with the first sprinkler as close to that point as
possible, but no further, while staying 6"

(152,4 mm)

 away from

the face of the trusses.  Remember the slope of the hip is not
equal to the slope of the roof from the ridge to the outside wall.
Continue to space sprinklers down the hip at a maximum of
6'-0"

(1,8 m)

 on center as measured along the slope of the hip.

When the bottom of the hip is encountered, the last sprinkler
must be within 7'-6"

(2,3 m)

 of the outside wall as measured flat

(plan view).  If this pipe is “cut to fit” remember to take into
account the different slopes the hip and the roof as well as
distances measured along the slope verses horizontal in plan
view.

•  Avoid obstructions as shown on page 9.  If necessary, add

standard sprinklers to maintain coverage around obstructions.

Figure 7

Figure 8

Figure 9

Branch Line

Ceiling

Truss

Ridge

6" (152,4 mm)

minimum

6"

(152,4 mm)

OR

CPVC

Non-Combustible Insulation

Non-Combustible

Insulation

6"

(152,4 mm)

Figure 10

Attic

Sprinkler

6" (152,4 mm) max.

6" (152,4 mm)

Insulation

1'-0"

(304,8 mm)

Joist

Non-Combustible Insulation

1'-0"

(304,8 mm)

Insulation of piping is for

fire protection, not

freeze protection.

OBSOLETE

Содержание CENTRAL Attic

Страница 1: ...the 60 second requirement to be met without an accelerator The other cost reduction is in the new Listing of BlazeMaster CPVC for Attic spaces feeding the wet system sprinklers below the ceiling Tradi...

Страница 2: ...monel thermal sensitive link The sprinkler frame orifice is sealed with a gasketed spring plate Belleville Seal consisting of a beryllium nickel disc spring that is sealed on both its inside and outs...

Страница 3: ...N VIEW 2 50 8 mm 1 2 NPT WRENCH FLAT ELEVATION VIEW Back to Back Dual Directional Attic Sprinkler BB1 17 32 BB2 17 32 BB3 17 32 Back to Back Dual Directional Attic Sprinkler BB1 BB2 BB3 HIP Sprinkler...

Страница 4: ...area above must be protected by Attic Sprinklers see figure 10 Insulation is for fire protection purposes It is not freeze protection BlazeMaster CPVC must be installed in accordance with the BlazeMas...

Страница 5: ...5mm than 10 3 0 m SD2 30 9 1 m to more 25 95 20 0 1 4 7 12 178mm 305mm to less than 10 12 254 mm 305mm than 10 3 0 m SD3 30 9 1 m to more 25 95 20 0 1 4 10 12 254mm 305mm to 12 12 305mm 305mm than 10...

Страница 6: ...kler Single Directional Attic Sprinkler Single Directional Attic Sprinkler Span Dimension Single Directional 16 406 4 mm minimum 22 558 8 mm maximum To Bottom of Sheathing Branch Line Ceiling Truss Ri...

Страница 7: ...the maximum spacing is 6 0 1 8 m and the minimum is 4 0 1 2 m see figures 2 11 The reason 400 square feet is not an issue with the single directional is because at its maximum spacing 6 0 1 8 m on cen...

Страница 8: ...ee figure 12 for joists perpendicular to outside wall Ridge Single Directional Attic Sprinkler Outside Wall 40 0 12 2 m maximum 3 0 0 9 m max on slope Back to Back Attic Sprinkler 6 0 1 8 m Max 6 0 1...

Страница 9: ...be 6 152 4mm clearance over the top of the obstruction to allow water to pass both over and under the obstruction The 6 152 4mm is measured perpendicular to the slope from the bottom of the joist If t...

Страница 10: ...rio To use attic sprinklers in these attics space attic sprinklers to protect the center portion of the building add standard sprinklers around the perimeter at a maximum of 7 0 2 1m and a minimum of...

Страница 11: ...tics having a mixture of standard spray sprinklers and Specific Application Attic SprinklersTM The design area requirements of NFPA 13 shall apply to all sprinkler types 5 Attics having a Width Greate...

Страница 12: ...ith the appli cable standards of the National Fire Protection Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The installing contractor or sprinkler m...

Отзывы: