E-2/3DB CONTROLLER
E:\Documents and Settings\Administrator\Local Settings\Temporary Internet Files\OLK3\E2-3DB.doc
Rev. 01/13/00; Rev. 07/2000 o2L/H
Rev. 10/2000 (dwgs. 100239, 601, 601-01, 601-02, H02-258, 100031, 279L, 274S, 100089)
Rev. 06/21/00 (Reformatted Text; Revised Pg. 3 (2.4.1, 20 amp to 30 amp)
Pg. 9
2.6.5 Power Failure (PF)
Connect the customer's alarm common to plug J3, to terminal #11.
Connect the customer's alarm wire to plug J3, terminal #12, for
normally open (or) terminal #10, for normally closed monitoring.
2.6.6 Photocell (PC)
Connect the customer's alarm common to plug J3, terminal #17.
Connect the customer's alarm wire to plug J3, terminal #18, for "off"
operation (or) terminal #16, for "on" operation monitoring.
2.6.7 Sidelight #1 Alarm (SA1)
Connect the customer's alarm common to Module M1, terminal T4.
Connect the customer's alarm wire to Module M1, terminal T5, for
normally open (or) terminal T6, for normally closed monitoring.
2.6.8 Sidelight #2 Alarm (SA2)
Connect the customer's alarm common to Module M2, terminal T4.
Connect the customer's alarm wire to Module M2, terminal T5, for
normally open (or) terminal T6, for normally closed monitoring.
2.7
ALARM TESTING
To test alarms, follow these procedures using an "ohm" meter between alarm
common and alarm points.
2.7.1 White Strobe Failure (ST1, ST2, and ST3)
White strobe failure testing can be performed in the day mode
operation. Check for status of strobe beacons. Turn "off" switch S1
on PCB #1 and status should change after a four (4) second delay.
After test, turn S1 to the normal operating position.
Содержание E-2/3DB
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......