89
2018/02
TBPN-L1
-FDIO1-2IOL- Saf
e
I/O
9.2
Status and Control Word
9.2.1
Status Word
The status word is mapped to the beginning of the process data.
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
-
Force
Mode
-
-
CFG
Error
COM
UV
V1
OV
V1
UV
V2
OV
V2
OC
Isys
-
CFG
change
d
-
-
DIAG
Name
Value Description
DIAG
0
-
1
Diagnostics available at the device.
CFG
changed
0
-
1
The device configuration was changed.
OC Isys
0
-
1
Overcurrent at Isys
OV V1/V2
0
-
1
V1 or V2 too high (> 30 V DC).
UV V1/V2
-
V1 or V2 too low (< 18 V DC).
COM
0
-
1
Internal error, the device-internal communication is disturbed.
CFG error
0
-
1
The configuration has been changed incompatibly.
Force Mode
0
-
1
The Force Mode is activated, which means, the actual output values may no match
the ones defined and sent by the field bus.
9.2.2
Control Word
The control word has no function.
Содержание TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Страница 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 16: ...About this user manual Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 8...
Страница 20: ...For Your Safety Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 12...
Страница 38: ...Mounting Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 30...
Страница 110: ...Operating Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 102...
Страница 116: ...Glossary of terms Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 108...
Страница 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...
Страница 165: ...Over 30 subsidiariesand over 60 representations worldwide www turck com 100000718 2018 02 100000718...