Add emergency shutdown in 64. OSSD
The release circuit remains unchanged as it corresponds to the standard configuration.
Emergency shutdown at SIL3-input FDI0/1, assigned to CIP Safety bit 1-7.
Fig. 34: 64. OSSD with emergency shutdown
Light grid (AOPD) in 63. OSSD
Delete the input element "Emergency shutdown".
Define the input as Safety electronical input in "Monitor settings
Local I/O".
Fig. 35: Define FDI2/3 as Safety electronical input
Select the light grid from the Device library and add it to the release circuit (OSSD) instead of the
emergency shutdown.
Содержание TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Страница 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 16: ...About this user manual Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 8...
Страница 20: ...For Your Safety Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 12...
Страница 38: ...Mounting Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 30...
Страница 110: ...Operating Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 102...
Страница 116: ...Glossary of terms Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 108...
Страница 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...
Страница 165: ...Over 30 subsidiariesand over 60 representations worldwide www turck com 100000718 2018 02 100000718...