IO-Link – Data Storage
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
28
3.3
Parameter "Data Storage Mode" = overwrite
The data set in the IO-Link master is
always
the reference data set.
The synchronization of the parameter sets is unidirectional towards to the device.
The status of the DS_UPLOAD_FLAG is ignored.
1
IO-Link-Master
IO-Link-Device
Para. IOLD =
parameter data of the IO-Link device
Fig. 5: "Data storage mode" = overwrite
3.4
Parameter "Data Storage Mode" = deactivated, clear
The data set in the IO-Link master is deleted.
The synchronization of parameter sets is deactivated.
IO-Link-Master
IO-Link-Device
Para. IOLD =
parameter data of the IO-Link device
Fig. 6: "Data storage mode" = deactivated, clear
Содержание TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Страница 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 16: ...About this user manual Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 8...
Страница 20: ...For Your Safety Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 12...
Страница 38: ...Mounting Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 30...
Страница 110: ...Operating Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 102...
Страница 116: ...Glossary of terms Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 108...
Страница 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...
Страница 165: ...Over 30 subsidiariesand over 60 representations worldwide www turck com 100000718 2018 02 100000718...