Technical Data
24
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
13
Technical Data
Technical Data
Power supply
Operating/load voltage
24 VDC
Permissible range
20.4…30 VDC
Total current
Max. 4 A per module
Sensor/actuator supply VAUX
Connector C1…C8 from power supply, short-circuit proof,
max. 120 mA per connector, with diagnostics
Power loss, typical
≤ 3.5 W
Inputs
Number of channels
16 digital pnp inputs (EN 61131-2)
Type of input diagnostics
Group diagnostics
Signal voltage, low level
-3…5 VDC (EN 61131- 2, type 1 and 3)
Signal voltage, high level
11…30 VDC (EN 61131- 2, type 1 and 3)
Input delay
0.010 ms
Max. input current
15 mA
Potential isolation
Inputs to FE, 500 VDC
Outputs
Number of channels
16 digital pnp outputs
Type of output diagnostics
Group diagnostics
Output voltage
24 VDC from supply voltage
Output current per channel
0.5 A, short-circuit-proof
Output delay
0.15 ms
Load type
Ohmic, inductive lamp load
Potential isolation
Outputs to FE, 500 VDC
IO-Link
IO-Link specification
Specified according to version 1.1
Parameterization
FDT/DTM, IODD
Transmission rate
COM 2: 38.4 kbit/s
Transmission physics
3-wire physics (PHY2)
Minimum cycle time
3.2 ms
Connectors
IO-Link
M12 × 1, 5-pole
Input/output
M12 × 1, 5-pole
Permissible torques
n
IO-Link
n
I/O channels
n
Mounting (M4 screws)
0.8 Nm
0.8 Nm
0.5 Nm
Standard/Directive conformity
Vibration test
According to EN 60068-2-6
Shock test
According to EN 60068-2-27
Drop and topple
According to IEC 60068-2-31/IEC 60068-2-32
Electro-magnetic compatibility
According to EN 61131-2/-6-4