Commissioning
Connecting the device to a Siemens PLC in PROFINET
52
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Example read access – read product name
Reading out the product name (product name, index 0x12) of the TURCK IO-Link I/O-hub TBIL-
M1-16DXP at IO-Link port 4.
Write the input variables of the function block via
control variable
as follows:
Variable
True
Meaning
REQ
TRUE
Send a read request
ID
264
Hardware identifier of the "Basic" slot according to the
configuration in the Device view
CAP
251
Function block instance
PORT
4
The I/O hub TBIL-M1-16DXP is connected to port 4.
IOL_INDEX
0x12
Index for product name
Fig. 47: IO_LINK_DEVICE – input variables for read access