Parameter name
Value
Meaning
Description
dec.
Hex.
0
0x00 No
The master transmits all IO-Link Events to the field-
bus.
1
0x01 Notifications
The master transmits all IO-Link Events to the field-
bus except for IO-Link notifications.
2
0x02 Notifications and warnings
The master transmits all IO-Link Events to the field-
bus except for IO-Link notifications and warnings.
3
0x03 Yes
The master doesn't transmit any IO-Link Event to
the fieldbus.
Process inpput
data mapping
(Mapping PDIN)
Optimization of the process data mapping for the used fieldbus: The I/O-Link-data can be
swapped depending on the used fieldbus in order to achieve an optimized data mapping on
the fieldbus side.
PROFINET:
With PROFINET, the parameter is permanently set to
0x00
= direct and cannot be changed.
0
0x00 direct
The process data are not swapped.
i.e.: 0x0123 4567 89AB CDEF
1
0x01 Swap 16 bit
The bytes are swapped per word.
i.e.: 0x2301 6745 AB89 EFCD
2
0x02 Swap 32 bit
The bytes are swapped per double word.
i.e.: 0x6745 2301 EFCD AB89
3
0x03 swap all
All bytes are swapped.
i.e.: 0xEFCD AB89 6745 2301
Process output
data mapping
(Mapping PDOUT)
see above
Process input data mapping
Vendor ID
0…65535
0x0000…
0xFFFF
Enter the IDs for the port configuration check.
Device ID
0…65535
0x0000…
0xFFFF
Содержание TBEN-S2-4IOL
Страница 1: ...Your Global Automation Partner Instructions for Use TBEN S2 4IOL IO Link Master Module...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 134: ...Over 30 subsidiaries and over 60 representations worldwide www turck com D301369 2019 10 D301369...