Operation Instructions

BotOn/BotOff/TopOn/TopOff

These parameters represent the switching threshold for 2-point and 4-point switching modes.  

The switching thresholds must not exceed the measuring range.

These parameters represent the switching threshold for 2-point switching modes:

Selection

Mode

Switching point

Range

BotOff

Under/NInv

G

0…f

max

TopOn

Under/NInv

G * (1 + H[%]/100 %)

< f

max

BotOn

Over/NInv

G * (1 - H[%]/100 %)

0…f

max

TopOff

Over/NInv

G

< f

max

BotOn

Under/Inv

G

0…f

max

TopOff

Under/Inv

G * (1 + H[%]/100 %)

< f

max

BotOff

Over/Inv

G * (1 - H[%]/100 %)

0…f

max

TopOn

Over/Inv

G

< f

max

These parameters represent the switching threshold for 4-point switching modes:

Selection

Mode

Switching point

Range

BotOff

NInv

G * (1 - 1.2 * H[%]/100%)

> 0

BotOn

NInv

G * (1 - H[%]/100%)

TopOn

NInv

G * (1 + H[%]/100%) 

TopOff

NInv

G * (1 + 1.2 * H[%]/100%)

0…f

max

BotOn

Inv

G * (1 - 1.2 * H[%]/100%)

> 0

BotOff

Inv

G * (1 - H[%]/100%)

TopOff

Inv

G * (1 + H[%]/100%) 

TopOn

Inv

G * (1 + 1.2 * H[%]/100%)

< f

max

Locking function

This parameter depends on the physical state of the relay. Parameter “Inversion” is regarded.

Selection

Description

Switched on

The relay switches on according to the measured value and selected 
configuration. It stays permanently locked on.
The locked state is left after power on reset or detection of a failure.

Switched off

The relay switches off according to the measured value and selected 
configuration. It stays permanently locked off.
The locked state is left after power on reset.

  Switching  on/off  delay

The value of this parameter specifies the switch on/off delay after detection of of switch on/off 

condition.

Values between 0.05…75 s are possible.

Selection

Description

(Ex, NEx)

On delay

The value of this parameter speci-
fies the switch on delay after detec-
tion of switch on condition.

0.0, 0.5, 0.75, 1.0 s

Off delay

The value of this parameter speci-
fies the switch off delay after detec-
tion of switch on condition.

0.0, 0.5, 0.75, 1.0 s

Содержание 3 IMX12-FI01-1SF-1R-0/24VDC/CC

Страница 1: ...Your Global Automation Partner Safety Manual IM X 12 FI01 1SF 1R Frequency Transducer...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com Contents...

Страница 3: ...r using the results 9 5 4 1 Probability of dangerous failure per hour High Demand Mode 9 5 4 2 Average probability of dangerous failure on demand Low Demand Mode 10 6 Operation Instructions 11 6 1 Gen...

Страница 4: ...4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 5: ...sh version of the safety manual or contact Turck directly 2 Scope This safety manual is valid for the following devices Product Number Product Name Number of Channels Terminal Block Design Power Bridg...

Страница 6: ...tential free contacts up to 10 kHz Outputs Common alarm output MOSFET potential free Relay output SPDT monitoring overshoot undershoot and window limits working direction adjustable reaction time digi...

Страница 7: ...ee contacts 1 Hz 10 kHz pulse pause ratio 50 s external signal source 1 Hz to 10 kHz pulse pause ratio 50 s 0 signal 0 3 V 1 signal 5 30 V The local process safety time is the periodical internal diag...

Страница 8: ...directly 5 1 Architectural specifications Due to architectural considerations the following characteristics are specified Type B HFT 0 Experience has shown that the useful lifetime often lies within...

Страница 9: ...29500 based on the average ambient temperature of components of 40 C No effect is a failure mode of a component that plays part in implementing the safety func tion but is neither a safe nor a danger...

Страница 10: ...Average probability of dangerous failure on demand Low Demand Mode With the FMEDA results and the values specified in the following table the average frequency of dangerous failure can be calculated...

Страница 11: ...om the temperature in the control cabinet The temperature on the exterior sidewall of the housing must be observed in a steady state In case the temperature on the exterior sidewall of the housing is...

Страница 12: ...Connection and Wiring Diagrams on page 20 Use cables with terminal cross section rigid 0 2 mm2 to 2 5 mm2 or flexible 0 2 mm2 to 2 5 mm2 When wiring with stranded wires Fix the wiring ends with ferrul...

Страница 13: ...Pull the screwdriver to fix the cable ends Fig 3 Connection with spring type terminals Make sure that only suitable equipment e g sensors are connected to the device see Ap pendix Connection and Wirin...

Страница 14: ...Voltage signal 0 signal 0 3 V 1 signal 5 30 V 3 wire PNP 3 wire sensor positive negative positive 0 signal sensor not actuated 0 V 1 signal sensor actuated 12 V 3 wire NPN 3 wire sensor negative posi...

Страница 15: ...g behavior when inversion is deactivated Fig 4 2 point mode 4 point In 4 point mode a window with a lower and upper hysteresis is formed The switch points must fulfill the following condition BotOff B...

Страница 16: ...x BotOn Inv G 1 1 2 H 100 0 BotOff Inv G 1 H 100 TopOff Inv G 1 H 100 TopOn Inv G 1 1 2 H 100 fmax Locking function This parameter depends on the physical state of the relay Parameter Inversion is reg...

Страница 17: ...cy is higher than the adjusted value the device falls into the safe state Config If the parameters are set push config button between 2 and 6 seconds In this way the device takes over the set values I...

Страница 18: ...lly charging cleaning agent Perform proof tests after each cleaning see Appendix Proof Test on page 22 The device must be replaced before remaining longer than 24 h within the safe state due to an int...

Страница 19: ...19 V01 00 2020 04 6 5 After operation Undo the terminal connection on the device Remove the device from its rail fixing as shown in the figure Fig 7 Remove device Ensure the dispose of the device...

Страница 20: ...rve The load curve of the relay A1D must be observed The relay must be protected against overcurrent IMX12 FI01 1SF 1R A 10 0 1 0 5 1 2 5 20 V 50 100 200 300 400 10 DC resistive load AC resistive load...

Страница 21: ...detected safe failure rate per hour MTTR Mean time to restoration hour PFDavg Average probability of dangerous failure on demand PFH Probability of dangerous failure per hour SFF Safe Failure Fraction...

Страница 22: ...ction 1 Bypass the safety functions and take appropriate action to avoid a false trip 2 Provide appropriate input control signals to the interface modules and verify the expected signal input output c...

Страница 23: ...23 V01 00 2020 04...

Страница 24: ...100017761 2020 04 100017761 Over 30 subsidiaries and over 60 representations worldwide www turck com...

Отзывы: