Operation Instructions
6.2
Before operation
➤
Fasten the device to a rail according to EN 60715 (TH35) as follows:
Fig. 1: Fasten the device
➤
Connect cables according to the wiring diagrams in
„Appendix: Connection and Wiring
.
➤
Use cables with terminal cross section
ū
rigid: 0.2 mm
2
to 2.5 mm
2
or
ū
flexible 0.2 mm
2
to 2.5 mm
2
➤
When wiring with stranded wires: Fix the wiring ends with ferrules.
Connection via screw terminals
➤
Insert the stripped cable ends (7 mm) in the guides of the cable glands.
➤
Fasten the screws with a screwdriver (max. tightening torque 0.5 Nm) to affix the cable ends.
Fig. 2: Connection with screw terminals
0.5 Nm
(4.43 LBS-inc)
0.2…2.5 mm
2
(24…13 AWG)
1
2
7 mm