14
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Operation Instructions
6.3
Parameterization
The user must select the parameters suitable for its safety application.
6.3.1
Parameters
The parameters are set using the switches on the housing side.
This is done with the help of a screwdriver.
If the teach button is pressed for 3 s, the parameters are adopted.
Sensor type
Selection
Description
NAMUR
NAMUR sensor according to EN 60947-5-6
– 0-signal: sensor not actuated
– 1-signal: sensor actuated
Switch
Potential free contact
– 0-signal: switch open
– 1-signal: switch closed
Voltage signal
Voltage signal:
– 0-signal 0…3 V
– 1-signal 5…30 V
3-wire PNP
3-wire sensor (positive, negative, positive)
– 0-signal: sensor not actuated (0 V)
– 1-signal: sensor actuated (12 V)
3-wire NPN
3-wire sensor (negative, positive, negative)
– 0-signal: sensor not actuated (12 V)
– 1-signal: sensor actuated (0 V)
Line monitoring (for NAMUR-sensors):
Selection
Description
Off
Line monitoring is switched off
Wire break and short circuit
Line monitoring short circuit and wire break
Parameters:
Switch
Parameter
State
Comment
S1
Line monitoring
OFF/ON
OFF/ON
S2
Relay mode
2P/4P
(2-point)/(4-point)
S3
2P: Under/Overspeed
Under/Over
Under-/Overspeed
S4
Relay diretion
Ninv/inv
(not inverted)/(inverted)
S5
Function Relay Loc
OFF/ON
OFF/ON
S6
Locked switching
LocOn/Locoff
Locked On/Locked Off
S7
SUD Input
[E2]/[E3]
Input [E2]/input [E2]
S8
SUD mode
Dyn/Stat
Dynamic/Static
Содержание 3 IMX12-FI01-1SF-1R-0/24VDC/CC
Страница 1: ...Your Global Automation Partner Safety Manual IM X 12 FI01 1SF 1R Frequency Transducer...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com Contents...
Страница 4: ...4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 23: ...23 V01 00 2020 04...
Страница 24: ...100017761 2020 04 100017761 Over 30 subsidiaries and over 60 representations worldwide www turck com...