Commissioning
Parameterizing readers with the DTM
38
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.1.9
Transferring the RSSI value – communication
The
Communication
tab is used to set the parameters for the configuration of the deBus
messages. All parameters and the settable values are written in the DTM.
Example: switch on RSSI transmission
Switch on RSSI transmission: choose
Communication
Ò
Message data content
Ò
Transponder RSSI
and select the
enabled
option.
a
The RSSI value is displayed with the inventory in the read data.
Fig. 37: Switching on RSSI transmission