8

 

Service 

Changing filter 

We  recommend  changing  the  filter  and  cleaning  the  heat 

exchanger  once  or  twice  per  year.  Remember  to  disconnect  from 

the mains before opening the front. 

Open the front using a 6 mm Allen key (1). The locks are located 

behind  two  holes  in  the  side,  and  can  be  unlocked  by  turning  the 

Allen key anticlockwise, and locked by turning it clockwise. 

 

 

 

 

The  extraction  filter  (2)  is  easily  accessible  when  the 

cover  is  opened.  Pull  out  the  filter  and  replace  with  a 

new one. 

If 

the 

following 

is 

printed 

on 

the 

filter: 

"Staubluftseite/Dust Air Side", the text should face away 

from  the  heat  exchanger.  If  there  is  no  printed  text,  the   

filter cannot be fitted the wrong way round. 

 

To  remove  the  intake  filter,  unscrew  the  two  finger 

screws  (3).  The  cover  (4)  can  now  be  removed  and 

filter taken out.  

Ensure  the  filter  is  inserted  correctly  when  replacing 

with  a  new  one.  The  side  which  must  face  away  from 

the heat exchanger (downwards according to the figure) 

has the following printed text: "Staubluftseite/Dust Air 

Side".  If  there  is  no  printed  text,  the  filter  cannot  be 

fitted the wrong way round.  

Replace the cover and tighten the finger screws. 

Содержание TX 75A

Страница 1: ...TURBOVEX TX 75A Installation operation and maintenance manual Revision 2013 06 13 ...

Страница 2: ...lation 5 Dimensioned drawing 5 External measurements 5 Mounting frame external measurements 5 Placing 6 Installation on wall window 6 Window installation diagrams for TX 75A 7 Service 8 Changing filter 8 Cleaning the heat exchanger 9 Mains connection 10 Retrofitting a TX controller 11 Technical specifications 12 EU Declaration of Compliance 13 ...

Страница 3: ... Incorrect use The window models are not designed for point extraction and are therefore not suitable for this purpose The unit is not fitted with a condensate pump or drain and should not be used in humid environments such as bathrooms Deliverables Ventilation unit including TX control system Mounting components Mounting frame 4 x M6 machine screws Optional extras TX controller control panel CO2 ...

Страница 4: ...temperature is higher than the room temperature The air volume can be adjusted using a CO2 sensor optional extra to ensure the level of air change is in line with activity in the room Figure 1 Function principle Outdoor air is sucked in by the intake motor and blown through the intake filter The air then passes through the heat exchanger and out via the intake grille into the room Room air is suck...

Страница 5: ...5 Installation Dimensioned drawing External measurements Figure 2 External dimensions in mm Mounting frame external measurements Figure 3 Mounting frame external dimensions in mm ...

Страница 6: ... window to be retained by min 3 frame fixing screws The hole in which the unit is fitted must be minimum 200 mm wide and 1210 mm high to take the mounting frame The mounting frame supplied is attached to the reinforcement and wall or between two reinforcements if the unit is placed between two windows using suitable screws Connect the unit to mains electricity and fit it in the mounting frame usin...

Страница 7: ...7 Window installation diagrams for TX 75A ...

Страница 8: ... a new one If the following is printed on the filter Staubluftseite Dust Air Side the text should face away from the heat exchanger If there is no printed text the filter cannot be fitted the wrong way round To remove the intake filter unscrew the two finger screws 3 The cover 4 can now be removed and filter taken out Ensure the filter is inserted correctly when replacing with a new one The side w...

Страница 9: ...voids damaging the hinges To remove the heat exchanger remove the cover 2 To do so remove the 8 screws 3 with a Philips screwdriver When the heat exchanger is out clean it carefully with a vacuum cleaner Reassemble the unit after cleaning Ensure the heat exchanger is correctly positioned The visible ribs on the sides must face downwards and to the right and upwards and to the left respectively 1 x...

Страница 10: ...lamp fitted behind the cover on the end of the unit Remove the cover by removing the four screws M3 x 10 mm Pass the cable through the middle cable grommet in the cover and connect the three wires to Phase Neutral and PE NB Mains connection must only be performed by an authorised electrician ...

Страница 11: ...iddle screws Secure the controller to the holder using 2 screws from the back The cable can be shortened if necessary Note wire colours and their positions to ensure correct re installation Pass the cable through the rubber grommet in the cover and through the cable holders along the inside of the unit on the left and fit the SUB D socket in the socket on the partition plate at the top of the unit...

Страница 12: ...0 x 241 x 1210 mm TX 75A Dimensions WxDxH mm 180 x 336 x 1200 Capacity m3 h 75 Weight kg Filter class F5 Standby Operation A Operation B Forced Noise level dB A 30 35 47 Flow m3 h 50 75 135 Energy consumption W 7 6 13 17 51 cos φ 0 55 0 5 0 5 0 5 SEL J m3 936 838 1360 Temperature efficiency 88 1 ...

Страница 13: ... 2011 Safety of machinery General principles for design Risk assessment and risk reduction DS EN 60269 1 A1 2009 Low voltage fuses Part 1 General requirements IEC 60269 1 1998 supplement A1 2005 to DS EN ISO 13857 2008 Safety of machinery Safety distances to prevent hazard zones being reached by upper and lower limbs DS EN ISO 1 2007 Electromagnetic compatibility EMC Part 6 1 Generic standards Imm...

Отзывы: