PCM30U, PCM30U-OCH – User's, Operating and Maintenance Manual
The output power can be doubled, if necessary, by parallel combination of the outputs of both power
amplifiers for a maximum output power capacity of up to 10 VA (setting
C
in technical parameters).
______________________________________________
!!! Note
:
Digital delay (ms1, +ms2) may not be used in a unit set for the “Comparison Protection” function,
because an actual time delay is involved, which would then cause delayed response to overvoltage or short circuit on the
protected power line (analogue delay or phase lead is in fact phase shift through the analogue corrector of phase, which
does not cause any change to the actual time delay in the signal transmission).
______________________________________________
Power Channel Modules
E-31