PCM30U, PCM30U-OCH – User's, Operating and Maintenance Manual
E.1.7 PBS Technical Parameters
E.1.7.1 General parameters
Number of bi-directional commands
10 (4)
Acknowledge input (ACK)
1
Transmission and security time (Tts)
additional security (repeating)
transmission
speed
1x (basic)
2x
4x
64 kbps
2 ms
4 ms
8 ms
128 kbps
1 ms
2 ms
4 ms
256 kbps
0,5 ms
1 ms
2 ms
Acting at output time (Ta)
Output
Switch on
Switch off
1 ÷ 4
1 ms
4 ms
5 ÷ 10
1 ms
1 ms
Complete transmission time is summation of Tts + Ta +Ttp. Ttp is additional delay caused by transmission
path.
HW unit configuration
Unit identification – A direction
4 bit address by switches on the unit
Unit identification – B direction
4 bit address by switches on the unit
nominal input voltage
individual jumpers for each command
on / off switch error outputs
individual jumpers for each
on / off switch command outputs
switch off only on demand while order (assembly option)
SW unit configuration
Input command digital filtering
0÷48 ms
±1 ms
Prolonging of command at input
0÷10 000 ms
±10 ms (0 - 1200 ms)
±100 ms (1200 – 10 000 ms)
Shortening of command at output
0÷1 000 ms
±1 ms (0 - 120 ms)
±10 ms (120 – 1000 ms)
Add, and, blocking at input
Blocking and kvit at output
Only one function of kvit and blocking can be used,
because of they use commonn input KVIT.
Capacity of unit‘s command log
1000 records
Capacity of the DORIS command log
Depending on the hard disk free space
DORIS
Counter of transmitted commands
Optionally display (0-999)
DORIS
Counter of received commands
Optionally display (0-999)
Operation
Error
Test
Command sending (10x LED)
Status indications by LED on panel
Command receiving (10x LED)
Urgent, non-urgent, service alarm
Line interface status (only PWA)
Unspecific error – must be identified by DORIS
DIN 41612 type E
Crimp contacts
CFVA 48, type E, 48 pin with grub screws for 10 commands
Command interface
connector
DIN E 32, type E, 32 pin with grub screws for 4 and 6 commands
Power Channel Modules
E-15