- 26 -
Table of parameter settings
No.
Parameter
Data
Step
Description
Default
setting
1 Parameter Lock
(1)Unlocked
Parameters can be changed.
(1)
(2)Locked
Parameters cannot be
changed.
2 Motor Voltage
(1)200-230V
3-phase, 200 V class
motor voltage
(1)
(2)380-460V
3-phase, 400 V class
motor voltage
3 Motor kW
(1)0.1kW
(11)15kW
Motor capacity setting
(4)
0.75kW
(2)0.2kW
(12)18.5kW
(3)0.4kW
(13)22kW
(4)0.75kW
(14)30kW
(5)1.5kW
(15)37kW
(6)2.2kW
(16)45kW
(7)3.7kW
(17)55kW
(8)5.5kW
(18)75kW
(9)7.5kW
(19)90kW
(10)11kW
(20)110kW
4 Start Time
0.1 to 20.0 s
0.1 s
Start Time setting
3.0
5 Process
1 to 8
1
No. of processes to be used
1
6 High2 Level
-200 to 5%,5 to 200%
1
Value of upper limit 2
for process 1
100
7
Shock Time
MIN
(30 ms) Shock Time setting for
upper limit 2
1.0
H2
0.1 to 10.0 s
0.1 s
8
Output Relay
(1)Self-Hold
Output operation mode
selection (High2)
(1)
H2
(2)Auto-Reset
9 High1 Level
-200 to 5%,5 to 200%
1
Value of upper limit 1
for process 1
80
10
Shock Time
MIN
(30 ms) Shock Time setting for
upper limit 1
1.0
H1
0.1 to 10.0 s
0.1 s
11
Output Relay
(1)Self-Hold
Output operation mode
selection (High1)
(2)
H1
(2)Auto-Reset
12 Low Level
-99 to 0 to 99%
1
Value of lower limit for
process 1
0
13
Shock Time
MIN
(30 ms) Shock Time setting for
lower limit
1.0
L
0.1 to 10.0 s
0.1 s
14
Output Relay
(1)Self-Hold
Output operation mode
selection (Low)
(1)
L
(2)Auto-Reset
15
Motor
Efficiency
10 to 100%
1
Motor efficiency
100
16 Response
1 to 50
1
No. of moving averaging times
5
17 Inhibit Time
IH
Inhibit time setting
IH
0.1 to 10.0 s
0.1 s
18 Auto Inhibit
(1)On
Auto Inhibit setting
(2)
(2)Off
19 POWER/TORQUE
(1)POWER
Monitoring of motor
input power value
(1)
(2)TORQUE
Monitoring of torque
calculated from power
20
H2 Relay
Logic
(1)Fail safe
Fail safe setting
(2)
(2)Normal logic
21 Output Select
(1)-200→200%
Analog output setting
(2)
(2)0→200%
22 LCD Backlight
(1)Always
Backlight illumination
time setting
(1)
(2)2min
23 Trip Test
(1)Motor On/Off
Selection of Test mode
setting while motor is
running
(1)
(2)Motor Off