Model
Item
㻌㻌 㻌 㻌 㻌 㻌 㻌 㻌 㻌
TSBSB05
TSBSB10
TSBSB30
TSBSB60
TSBSB100 TSBSB200
TSBSB300
Current setting*
䠍
0.5
䡚
6A
1
䡚
12A
3
䡚
30A
5
䡚
60A
10
䡚
100A 20
䡚
200A 30
䡚
300A
Time
setting*
䠍
Start Time
*
䠎 㻌
0.2
䡚
10s
Shock Time
*
䠎 㻌
0.2
䡚
5s
Accuracy
±10%
䠄
Full Scale
䠅
Control Power Supply
24
䡚
240VAC/DC
䠄
No
polarity
䠅
±10
䠂
50/60Hz
Maximum motor voltage
AC600V 50/60Hz
㻌
*
䠏
Current sensing method
2 Integral Current Transformer
Display
Monitoring state,
䛂
MON
䛃
lamp on
㻌
Overcurrent state,
䛂
OC
䛃
lamp on
Output
Relay
Contact
constitution
1a1b
Contact rating
3A
㻌
AC250V
䠿
os
φ
䠙䠍
Recommend
current
(High-frequency
operation )
0.2A or less
㻌
AC250V cos
φ
䠙
0.4
Minimum
allowable load*
䠐
DC10V,10mA
Operation
selecting*
䠑
䠠䠥䠬
switch selection
䠯䠯䠖
Normal operation/excitation; self-holding after trip
㻌 㻌 㻌 㻌 㻌 㻌
㻌 㻌 㻌
㻌
䠯䠝䠖
Abnormal/excitation; automatically reset after trip
Expected life
80,000 times at rated load
Operating
temperature
䠉
20
䡚䠇
60
Υ
Ambient
Environment
Storage
temperature
䠉
30
䡚䠇
70
Υ
Humidity
45
䡚
85% RH without condensation
Altitude
2,000m or less
Pollution degree
Class 3, free from dust and corrosive gas
Vibration
5.9m
䠋
s
2
or less
Insulation
Between casing and
circuit
Over 10M
Ω
䠄
DC500V Megger
䠅
Dielectric
Strength
Between casing and
circuit
AC2000V
䠈
60Hz
䠈
1min
Between contacts
AC1000V
䠈
60Hz
䠈
1min
Between circuits and
contacts
AC2000V
䠈
60Hz
䠈
1min
Protection structure
IP20
Material
Case
Upper case
䠖䠬䠝䠒䠈
Lower case
䠖䠬䠝䠒䠒
Terminal cover
䠬䠝䠒
Power Consumption
2W or less
Mounting
35mmDIN rail or Panel
Weight
Main body
䠄
External CT
䠅
0.2 kg
㻌 䠄
0.5k
䡃䠅
*1. Current
࣭
Time setting ranges are settable ranges, not the upper or lower level of setting knob.
*2. The minimum value on the display is 1s, values smaller than 1s can be set with the dial.
*3. In the case of inverter drive, there is a possibility of malfunction due to the distortion of the current waveform. If the
frequency is within the range of 30 to 60Hz, it can be used because the influence is minor.
*4. Be sure to input minute electric currents through the relay when inputting an output relay contact directly into the PLC
(Programmable logic controller), because there is a risk of contact failure due to minute electric current.
*5. DIP switch is set on SS side when delivery.
*6. When power off to reset, power off more than 1 seconnd.
*7. Certificate standard : UL certification
–
UL508, CCC certification
–
GB14084.4