32 

Part Two 

 

The ANALOG OUT item is used to vary the analog output from the SureFlow 
unit. When this item is entered, a number will be shown on the display indicating 
the last analog output value. The value displayed ranges from 0 to 255. The 
value 255 corresponds to the lowest voltage (current) output and 0 corresponds 
to the highest voltage (current) output. Pressing the 

 key will decrease the 

analog output and increase the value displayed. Pressing the 

 key will 

increase the analog output and decrease the value displayed. 

 
 

The ANALOG OUT function can be used in conjunction with a volt meter to verify 
the analog output is correct.  

 

Switch Input 

Menu Item - SWITCH INPUT

 

The SWITCH INPUT

 

item reads the input of the SWITCH IN contact pins 11 and 

12. When this item is entered, the display will indicate either open or closed.  If 
the display indicates open, the DIM is in LOW ALARM, HIGH ALARM and 
ALARM DELAY mode. If the display indicates closed, the DIM is in REM LOW 
ALM, REM HIGH ALM, and DOOR DELAY mode.  
 
SWITCH INPUT changes both alarm and alarm delay when closed. If the same 
alarm or alarm delay is required, set both alarms or delays to same value.  

 

Flow Input 

Menu Item - FLOW INPUT 

 

The FLOW INPUT

 

item is used to read the input from the flow station. When this 

item is entered, a voltage will be indicated on the display. The exact voltage 
displayed is relatively unimportant. It is more important that the voltage is 
changing which indicates the flow station is working correctly.     

0 volts displayed equals zero flow. 
5 volts displayed equals 2832 ft/min x duct area (ft

2

)

 

- pressure based 

flow station. 

5 volts displayed equals TOP VELOCITY x duct area (ft

2

)- linear flow 

stations (see Configure menu, TOP VELOCITY item). 

 

Low Alarm Relay 

Menu Item -

 

LOW ALM REL

 

The LOW ALM REL item is used to change the state of the low alarm relay. 
When this item is entered, the display will indicate either OPEN

 

or

 

CLOSED. 

The 

/

 keys are used to toggle the state of the relay. The 

 key is used to 

OPEN the alarm contact. The 

 key is used to CLOSE the alarm contact. When 

the contact is closed, the LOW ALM REL should be in an alarm condition. 

 

High Alarm Relay  

Menu Item -

 

HIGH ALM REL 

The HIGH ALM REL item is used to change the state of the high alarm relay. 
When this item is entered, the display will indicate either OPEN or CLOSED. The 

/

 keys are used to toggle the state of the relay. The 

 key is used to OPEN 

the alarm contact. The 

 key is used to CLOSE the alarm contact. When the 

contact is closed, the HIGH

 

ALM

 

REL should be in an alarm condition. 

 

Содержание SUREFLOW 8635-M

Страница 1: ...SUREFLOW ROOM PRESSURE MONITOR MODELS 8635 M OPERATION AND SERVICE MANUAL P N 1980272 REVISION E FEBRUARY 2013...

Страница 2: ......

Страница 3: ...RY 2013 U S AND CANADA OTHER COUNTRIES Sales Customer Service Sales Customer Service 800 874 2811 651 490 2811 001 651 490 2811 Fax Fax 651 490 3824 001 651 490 3824 SHIP MAIL TO E MAIL TSI Incorporat...

Страница 4: ...ENT AND EXCLUDES CLAIMS OF CONTRIBUTORY OR INDUCED INFRINGEMENTS BUYER S EXCLUSIVE REMEDY SHALL BE THE RETURN OF THE PURCHASE PRICE DISCOUNTED FOR REASONABLE WEAR AND TEAR OR AT SELLER S OPTION REPLAC...

Страница 5: ...the SureFlow unit functions and how to interface with the device This section should be read by users facilities staff and anyone who requires a basic understanding of how the SureFlow monitor operat...

Страница 6: ...iv This page intentionally left blank...

Страница 7: ...d is the first level of containment and the laboratory itself is the second level of containment Room pressure or pressure differential is created when one space hallway is at a different pressure tha...

Страница 8: ...providing instant information on the room pressure Useful User Information The DIM has a green light and red light to indicate room pressure status The green light is on when the room has proper room...

Страница 9: ...eration green light is on the display continuously scrolls information about room pressure and other variables programmed flow air changes per hour etc The variables that scroll depend on the options...

Страница 10: ...ee MUTE TIMEOUT When the mute period ends the audible alarm turns back on if the alarm condition is still present NOTE The user can program the audible alarm to be permanently turned off see AUDIBLE A...

Страница 11: ...nches H2O When the room pressure drops below 0 001 inches H2O gets closer to zero the audible and visual alarms activate The alarms turn off when set to unlatched when the unit returns to the safe ran...

Страница 12: ...it 8635 M ____ Software revision level Facility where unit is installed First two items that scroll when TEST key is pressed Due to the different SureFlow models available the above information is nee...

Страница 13: ...another etc The menu items and all related information is listed in table format and includes programming name description of menu of item range of programmable values and how the unit shipped from t...

Страница 14: ...m or configure the unit to fit your particular application Programming the instrument will change how the unit functions so thoroughly review the items to be changed Figure 4 Programming Keys MENU Key...

Страница 15: ...ressing the arrow key will scroll through the values faster than if arrow key is pressed and released Keystroke Procedure The keystroke operation is consistent for all menus The sequence of keystrokes...

Страница 16: ...essure is shown in this case PRESSURE 00085 H2O Press the MENU key to gain access to the menus MENU The first 2 menu choices are displayed ALARM CONFIGURE Press the SELECT key to access the ALARM menu...

Страница 17: ...nd the menu item on the bottom line goes to step 3 ALARM HIGH ALARM WARNING If the MENU key was pressed instead of the SELECT key the new data would not have been saved and the SureFlow monitor would...

Страница 18: ...n provides the following information Complete list of menu and all menu items Gives the menu or programming name Defines each menu item s function what it does how it does it etc Gives the range of va...

Страница 19: ...FLO STA TYPE TOP VELOCITY ROOM VOLUME ACCESS CODE CALIBRATION SENSOR ZERO SENSOR SPAN FLOW ZERO ELEVATION ACCESS CODE INTERFACE NET PROTOCOL NET ADDRESS OUTPUT RANGE OUTPUT SIG ACCESS CODE DIAGNOSTICS...

Страница 20: ...pins 11 and 12 is open or the RS 485 communications sends a command OFF 0 to 0 19500 H2O 0 to 0 19500 H2O OFF REMOTE OR SECOND LOW ALARM REM LOW ALM The REM LOW ALM item sets a remote or second low pr...

Страница 21: ...cally resets the alarms when the unit reaches the safe pressure range LATCHED requires the staff to press the RESET key after the unit returns to the safe pressure range The ALARM RESET affects the au...

Страница 22: ...and ALARM DELAY are turned off Set the remote alarms equal to the standard alarms if the same alarms are required delay would just change 20 to 600 SECONDS 20 SECONDS MUTE TIMEOUT MUTE TIMEOUT The MU...

Страница 23: ...remote can be programmed for positive or negative pressure However both the low and high alarm must be set either positive or negative The DIM does not allow one positive alarm and one negative alarm...

Страница 24: ...ssure sensor high alarm Flow station minimum flow Data error 9 The low and high alarms are absolute values The chart below shows how the values must be programmed in order to operate correctly 0 2 inc...

Страница 25: ...ct area if programmed the display will automatically scroll the actual flow as part of the display sequence If a zero value is entered the flow value will not scroll on the display If the DIM displays...

Страница 26: ...the ROOM VOLUME and the input from the air flow station If no flow station is installed a zero value should be entered 0 to 20 000 cubic feet 0 to 550 cubic meters The DIM does not compute volume The...

Страница 27: ...ollowing menu item listing NONE Unit is factory calibrated No initial adjustment should be necessary FLOW ZERO FLOW ZERO The FLOW ZERO item is used to establish the flow station zero flow point A zero...

Страница 28: ...S CODE item prevents unauthorized access to a menu If the ACCESS CODE is ON a code is required before the menu can be entered Conversely if the ACCESS CODE is OFF no code is required to enter the menu...

Страница 29: ...will initiate a change RS 485 communications allows the user access to all menu items except calibration items The RS 485 network can initiate a change at any time 1 to 247 1 OUTPUT RANGE OUTPUT RANG...

Страница 30: ...ACCESS CODE item selects whether an access code pass code is required to enter the menu The ACCESS CODE item prevents unauthorized access to a menu If the ACCESS CODE is ON a code is required before...

Страница 31: ...the door middle of door edge of door etc A thermal air velocity meter is needed to make the comparison measurement Normally the velocity is checked at the crack under the doorway or the door is opene...

Страница 32: ...can only occur at very low pressures so slightly changing the balance should eliminate the problem Perform a smoke test to determine pressure direction Select SENSOR SPAN item Position thermal air vel...

Страница 33: ...cutoff flow in duct Flow station must have no flow going past sensor Enter calibration menu Access code is required Select FLOW ZERO to take flow zero Press SELECT key Flow zero procedure which takes...

Страница 34: ...e white and free of accumulated debris Figure 7 Pressure sensor door slid open Periodically inspect the other system components for proper performance and physical signs of excessive wear Pressure Sen...

Страница 35: ...configuration problems or interaction problems with the HVAC system The hardware test described in this section determines that all TSI mechanical components are functioning correctly The hardware te...

Страница 36: ...T DIM Press TEST key to verify Digital Interface Module DIM electronics are functioning correctly At the end of the self test the display will show SELF TEST PASSED if all DIM electronics are good If...

Страница 37: ...ts normal state Sensor Input Menu item SENSOR INPUT The SENSOR INPUT item is used to verify that the DIM is receiving a signal from the sensor When this item is entered a voltage will be indicated on...

Страница 38: ...put Menu Item FLOW INPUT The FLOW INPUT item is used to read the input from the flow station When this item is entered a voltage will be indicated on the display The exact voltage displayed is relativ...

Страница 39: ...elects whether an access code pass code is required to enter the menu The ACCESS CODE item prevents unauthorized access to a menu If the ACCESS CODE is ON code is required before the menu can be enter...

Страница 40: ...Verify circuit breaker is on Verify transformer primary measures 110 VAC Verify transformer secondary measures 24 to 30 VAC If proper voltage is found between pins 1 and 2 of the DIM all wiring has b...

Страница 41: ...be unique for each DIM Data sent to DIM may be in form that the SureFlow monitor cannot recognize DIM displays opposite pressure signal Sensor direction is incorrect Pressure sensor must have dip swi...

Страница 42: ...wildly fluctuating Exhaust or supply system unstable Supply or exhaust air is affecting the sensor Check supply and exhaust flow for stability Verify reference pressure is not fluctuating Check locati...

Страница 43: ...150 VDC 250 VAC Maximum switch load 10 mA 5 VDC Contacts close in alarm condition Analog Output Type 0 to 10 VDC or 4 to 20 mA Range High 0 100 to 0 100 inches H2O Low 0 0100 to 0 0100 inches H2O Reso...

Страница 44: ...38 Appendix A This page intentionally left blank...

Страница 45: ...put When input is closed these software items are enabled REMOTE LOW ALARM REMOTE HIGH ALARM and DOOR DELAY 13 14 Output Low alarm relay N O closes in low alarm condition See menu items LOW ALARM REMO...

Страница 46: ...40 Appendix B...

Страница 47: ...n an access code is required pressing the following key sequence will provide access to the required menu Key Alarm Configure Calibration Interface Diagnostics 1 TEST EMERGENCY AUX TEST TEST 2 TEST ME...

Страница 48: ...42 Appendix C This page intentionally left blank...

Страница 49: ...more information USA Tel 1 800 874 2811 UK Tel 44 149 4 459200 France Tel 33 4 91 11 87 64 Germany Tel 49 241 523030 India Tel 91 80 67877200 China Tel 86 10 8251 6588 Singapore Tel 65 6595 6388 P N 1...

Отзывы: