Technical Section
29
Replacement Parts
All components of the room pressure monitor are field replaceable. Contact TSI HVAC
Control Products at (800) 874-2811 (U.S. and Canada) or (001 651) 490-2811 (other
countries) or your nearest TSI Manufacturer's Representative for replacement part
pricing and delivery.
Part Number
Description
800222
Model 8635 Pressure Monitor
800326
Pressure Sensor
800248
Sensor Cable
800414
Transformer Cable
800420
Transformer
Troubleshooting Section
The SureFlow Room Pressure Monitor is designed to be trouble free. However,
installation problems or interaction with other HVAC components may cause system
problems. The SureFlow system is easy to trouble shoot if an organized approach to
evaluate the system is taken. Troubleshooting is broken down into hardware and
software problems. Hardware problems deal with the physical installation of the device.
Hardware problems include wiring problems, incorrectly installed equipment, and add-
ons or non TSI equipment. Software problems include configuration problems, or
interaction problems with the HVAC system.
The hardware test described in this section determines that all TSI mechanical
components are functioning correctly. The hardware test requires the diagnostics menu
items to be accessed. If you are unfamiliar with the SureFlow monitor menus, see
Software Programming
for keystroke procedure. Troubleshooting the majority of
problems is usually quick if the hardware test is followed.
Software and hardware problems are covered in the troubleshooting chart. Pick the
problem that most closely resembles your problem and review the possible symptoms
and corrective action. Software or system performance problems can and are affected by
the supply air system, exhaust air system, or physical configuration of the room.
Separating TSI system problems from the HVAC system can sometimes be difficult. TSI
recommends confirming all hardware is operating correctly before troubleshooting
software problems.
Hardware Test
Three tests need to be performed in order to determine all hardware is functioning
correctly. The tests are broken down into:
Confirming wiring is correct.
Confirming physical installation is correct.
Verifying mechanical components.