
Technical Section
27
Linear flow station 1-5 VDC output
Remove flow station from duct, or cutoff flow in duct. Flow station must have no
flow going past sensor.
Enter calibration menu. Access code is required.
Select
FLOW ZERO
to take flow zero.
Press
SELECT
key. Flow zero procedure, which takes 10 seconds, is automatic.
Press
SELECT
key to save data.
Install flow station back in duct.
Содержание SUREFLOW 8635-M
Страница 2: ......
Страница 6: ...iv This page intentionally left blank...
Страница 44: ...38 Appendix A This page intentionally left blank...
Страница 46: ...40 Appendix B...
Страница 48: ...42 Appendix C This page intentionally left blank...