A
B
TAPI-8
TAPI-13
TAPI-15
TAPI-17
Technical Data
Power Requirements
16178
16174
Bench Drill
16180
1/2”
5/8”
120 V
Class I
60 Hz
Floor Drill
16182
10 ½” x 10 ½”
6” x 6”
12” x 12”
with insulating temperature of 221°F
18 AWG x 3C
16 AWG x 3C
13” x 13”
250 RPM - 3 000 RPM
760 RPM - 3 070 RPM
300 RPM - 3 000 RPM
5
12
3/4 HP
1/3 HP
1 HP
1
1
/
2
HP
6,6 A
2,5 A
9,5 A
Code
Description
Chuck
Work Bench
Voltage
Frequency
Current
Motor
Speeds
Range
Conductors
Insulation
Power Cord Grips used in this product: Type “Y”.
Tool Build Quality: Basic insulation
Thermal insulation on motor winding: Class B
3
* It is safe to use only if the extensions themselves have an artifact for over current protection. AWG = American Wire Gauge. Reference: NMX-J-195-ANCE
CAUTION
CAUTION
The tool shall be grounded while in use to prevent an
electric shock. • Connect the plug into a properly grounded outlet as shown in
example
A
. Not all the outlets are properly grounded. If in doubt verify with a
certified electrician. • If the outlet you plan to be using for the tool has two
poles (2 orifices).
FOR NO REASON AT ALL DO NOT REMOVE OR ALTER
THE GROUND CONDUCTOR IN THE PLUG.
Use a temporary adaptor as
shown in example
B
and always connect the ground lug as indicated.
When using an extension cable, verify the gauge is enough
for the power that the tool needs. A lower gauge cable will cause voltage drop in the line, resulting in power loss and the motor will
overheat. The following table shows the right size to use depending on cable’s length and the ampere capability shown in the tool’s
nameplate. When in doubt use the next higher gauge.
WARNING
When operating power tools outdoors use a grounded extension cable labeled “Outdoor Use”
brand. These extension cables are specially designed to be used outdoors and reduce the risk of an electric shock.
All the cabling, power connections and the ground connection in the system shall comply with the
OFFICIAL MEXICAN STANDARD NOM -001 - SEDE, INSTALACIONES ELÉCTRICAS (UTILIZACIÓN)
or with the local
codes and or local ordinances. The user shall contact a certified electrician.
WARNING
WARNING
WARNING
WARNING
Avoid the risk of electric shock or severe injury. When the power cable gets damaged
it should only be replaced by the manufacturer or at a Authorized Service Center.
The build quality of the electric insulation is altered if spills or liquid gets into the tool while in use.
Do not expose to rain, liquids and/or dampness.
Before gaining access to the terminals all power sources should be disconnected.
From 0 and up to 10 A
From 10 and up to 13 A
From 13 and up to 15 A
From 15 and up to 20 A
18 AWG
16 AWG
14 AWG
8 AWG
16 AWG
14 AWG
12 AWG
6 AWG
3 (one grounded)
From 5,9 ft to 49 ft | Higher than 49 ft
Ampere
Capacity
Number of
Conductors
Extension Gauge
ENGLISH
DRAFT
DRAFT
DRAFT
DRAFT
DRAFT