23
TRUE
traditional
reach
-
ins
www
.
truemfg
.
com
1
2
3
4
5
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
HOW TO CHANGE DISPLAY READOUT FROM
FAHRENHEIT TO CELSIUS:
May need to unlock control.
This can NOT be changed with the LAE model AR2-28 version of the control. See
page 32 for more information.
WHY:
Changing readout will assist with customer application.
HOW TO CHANGE DISPLAY READOUT FROM
FAHRENHEIT TO CELSIUS:
STEP 1
- To change the display, press and hold the Info button
and
the Stand-by button
at the same time. “MdL” or “SPL” will appear.
See images 1a and 1b.
STEP 2
- Push the Down button
until “ScL” appears. See image 2.
STEP 3
- Press and hold the Info button
to see the “readout scale”.
See image 3.
STEP 4
- While pressing and holding the Info button
, press the
up
or down
button to change the “readout scale".
See image 4.
STEP 5
- Once the “readout scale” has been changed, release the info
button
.
STEP 6
- Wait 30 seconds for the display to show temperature.
See image 5.
1a
1b
2
3
4
5