16                             Manual Number 9018067  •  Revision J, May 4, 2020 

  Under-Voltage 

When the input voltage drops below the operating range of the unit (See Section 1.2.1; 
absolute minimum input of 20VDC) the unit senses an under-voltage condition and disables 
the output. The unit will dynamically monitor the input voltage such that if the input returns 
to within the normal operating range, the output will be enabled and allow the unit to 
operate normally. Under-voltage will not activate the fault status output. 

  Over-Temperature 

The TI250 Series Static Inverter incorporates an internal temperature sensing device that 
continually provides monitoring and feedback to the control circuits. When the unit senses 
an internal condition that exceeds maximum temperature ratings, the output is disabled and 
the fault output will indicate. The inverter will continue to remain shut-down in a fault 
condition until the temperature returns to within acceptable limits. This over-temperature 
reset occurs automatically without external intervention required.  
 

  Short Circuit And Over-Current 

The TI250 Series Static Inverter is capable of surviving a short circuit or over-current event 
without permanent damage or effect to long-term reliability. The unit can provide over its 
rated power output up to 375 watts for over 30 minutes (until over-temperature shutdown 
occurs).  
The inverter monitors the AC output on a pulse-by-pulse scenario to determine a short-
circuit or over-current situation. If detected, the output is limited by clipping the AC sine 
waveform, limiting the power output. If the short-circuit or over-current situation continues 
for more than a few seconds, the inverter will turn-off the AC output and indicate a fault on 
the fault output line. 
 

  Ground Fault Protection (-1 only) 

The TI250 Series Static Inverter monitors the AC output for indications of current imbalance 
between the two AC output lines. Should a ground fault be detected, the AC output will be 
disabled and the fault output will indicate. Remove all inverter loads before re-enabling the 
inverter.  
 

  Fault Shutdown and Indication 

The TI250 Series Static Inverter monitors the AC output load, its internal temperature, and 
operation status. Should the load be excessive or the inverter become too hot, the inverter 
will disable the AC output and indicate a fault status on the fault output. If the inverter is in a 
fault state, a LED connected as shown in the wiring diagrams will be lit. 
 
To reset the inverter and clear the fault: 1) Remove all inverter loads before re-enabling the 
inverter, 2)Re-enable the inverter by switching the inverter OFF for four seconds, and then 
back to ON. NOTE: If the inverter is over-temperature it will not re-enable until it has 
cooled. Fault can also be cleared by cycling power to the inverter. 
 

 

 

Содержание 6430250-1

Страница 1: ...Revision J May 4 2020 ...

Страница 2: ...ruebluepowerusa com www mcico com We welcome your comments concerning this manual Although every effort has been made to keep it free of errors some may occur When reporting a specific problem please describe it briefly and include the manual part number the paragraph figure table number and the page number Send your comments to True Blue Power c o Mid Continent Instrument Co Inc Attn Technical Pu...

Страница 3: ...ING OF CABLES 6 2 4 LIMITATIONS 6 2 5 MODIFICATION 7 SECTION 3 INSTALLATION 8 3 1 GENERAL INFORAMATION 8 3 2 UNPACKING AND INSPECTING EQUIPMENT 8 3 3 CABLE HARNESS 8 3 4 MOUNTING 13 3 5 INSTALLATION COMPLETION 13 3 6 INSTALLATION CAUTION 14 SECTION 4 OPERATION 15 4 1 ELECTRICAL PERFORMANCE 15 4 2 PROTECTIVE FEATURES 15 SECTION 5 CONFORMANCE 17 5 1 INSTRUCTIONS FOR CONTINUED AIRWORTHINESS 17 5 2 EN...

Страница 4: ... Selection BMC D 01 02 2015 Added TI254 and TI256 models BMC E 05 11 2015 Added 4 Configuration BMC F 06 16 2015 Updated 4 Configuration specifications BMC G 01 06 2017 Update connector Pinout Table to agree with the input voltage in the Specification Table CAS H 07 26 2019 Updated altitude in Table 1 3 and Qualification sheet VAA J 05 04 2020 Updated style and brand to meet Marketing and Engineer...

Страница 5: ... dual unit synchronization The TI250 Series Static Inverter is FAA certified to TSO C73 and tested to rigorous environmental standards and levels of RTCA DO 160 The small size and light weight in conjunction with its installation flexibility inside or outside the pressure vessel make it an ideal choice for aircraft power needs while reducing the challenges associated with other similar products Hi...

Страница 6: ...ase pure sine wave Power Factor 0 8 to 0 8 Efficiency 87 90 nominal Total Harmonic Distortion THD Less than 2 Table 1 1 Physical Attributes Model TI250 Model TI254 Model TI256 Model TI256 Weight 2 2 lbs 1 kg 2 2 lbs 1 kg 2 6 lbs 1 15 kg 2 6 lbs 1 15 kg Dimensions not including connector mate 6 7 inches long x 6 0 inches wide x 2 0 inches high 171 mm long x 152 mm wide x 51 mm high Mating Connector...

Страница 7: ...es past the unit connector to allow for back shell access to the connector 2 3 ROUTING OF CABLES The wires and cable bundle associated with the unit are heavy gauge wire and carry significant power Be aware of routing cables near other electronics or with other wire bundles that may be susceptible to high energy flow Avoid sharp bends in cabling and routing near aircraft control cables Also avoid ...

Страница 8: ...plate by the lack of marking on the MOD numbers 1 through 9 i e 1 9 are visible All subsequent modifications are identified on the nameplate by the marking blacking out of that particular MOD number i e for MOD 1 the number 1 is not visible and 2 9 are visible see Figure 2 1 for examples MODs do not have to be sequentially inclusive and may be applied independent of each other For additional detai...

Страница 9: ... of Figure 3 3 Figure 3 4 and Wiring Diagram of Table 3 3 Refer to Section 2 Pre Installation Considerations in regards to routing precautions Wire Gauge Selection Use of PTFE ETFE TFE Teflon or tefzel insulated wire is recommended for aircraft use Use the following wire gauges for each of the pins in the connector Pin A and D 12 14 AWG stranded or solid Pin B and C 18 20 AWG stranded or solid Pin...

Страница 10: ...ll have approximately 16 VDC present internally limited to less than 3 mA If the inverter is to be enabled at all times pin E can be connected to pin G Remote ON OFF Return This pin is internally connected to pin D Pin G may be used as the return from an ON OFF switch or left unconnected It is recommended that pin G not be connected directly to ground or 28V negative INVERTER FAULT INDICATION OUTP...

Страница 11: ...115VAC Output AC Return C AC Return Remote On Off D DC Return 18 36VDC Input E Fault Indication 26VAC Output F Remote On Off Phase Sync G 26VAC Output 115VAC Output Connector Pinout Figure 3 4A Typical TI250 Small Aircraft Minimum Wiring Installation A D B E C F G Figure 3 3 Pinout View of Unit Connector Table 3 3 Connector Pinout OUTLETS A D G E B C 28VDC INVERTER ENABLE ON OFF TI250 15A Optional...

Страница 12: ...ixed Equipment TI254 A D G F B C 28VDC INVERTER ALWAYS 15A E 1 5K 1W FAULT LED CASE ATTACHED OR NOT ATTACHED TO AIRFRAME AIRCRAFT MONITORING SYSTEM FIXED AIRCRAFT EQUIPMENT ENABLED 2 5A 6430250 2 TI250 A D G E B C 28VDC INVERTER ENABLE ON OFF 15A F 1 5K 1W FAULT LED CASE ATTACHED OR NOT ATTACHED TO AIRFRAME OUTLETS 110VAC 1A NEU HOT 6430250 1 ...

Страница 13: ... 26VAC Fixed Equipment A D G E B C 28VDC TI250 15A F CASE ATTACHED OR NOT ATTACHED TO AIRFRAME OUTLET Optional Breaker 110VAC 2 5A HOT NEU AIRCRAFT CABIN ACCESSORIES SYSTEM 6430250 1 TI256 A D F G C B 28VDC 15A E 1 5K 1W FAULT LED CASE ATTACHED OR NOT ATTACHED TO AIRFRAME AIRCRAFT MONITORING SYSTEM 115V 400Hz EQUIPMENT 6430250 3 3A 26V 400Hz EQUIPMENT 2 5A ...

Страница 14: ...ting only Four 10 mounting holes should be provided in the aircraft in accordance with Figure 3 5 Secure the unit with four 10 pan head Phillips screws or equivalent A lock washer under the head of each screw is recommended 3 5 INSTALLATION COMPLETION Prior to operating the unit in the aircraft it is recommended to verify the output and functionality of the unit In order to prevent accidental dama...

Страница 15: ...rcumstance allow the output of the inverter to be connected to ground utility AC power or damage will result If more than 250 watts of power is required for an installation a higher power inverter model such as the 500 watt Mid Continent MD50 should be selected Connector per MS3102A 18 9P 2 0 4 75 5 0 5 50 5 94 4X Ø 22 10 32 Mounting Holes 6 0 0 7 Figure 3 5 TI250 Series Static Inverter Outline Dr...

Страница 16: ...r legacy designs that incorporate voltage mode controllers Additionally the AC output stage controls both the current and voltage of the output AC waveform providing a low distortion sine wave output even over varying power factor requirements of the load The AC output is frequency controlled using a crystal oscillator reference 4 2 PROTECTIVE FEATURES Remote On Off The TI250 Series Static Inverte...

Страница 17: ...or over 30 minutes until over temperature shutdown occurs The inverter monitors the AC output on a pulse by pulse scenario to determine a short circuit or over current situation If detected the output is limited by clipping the AC sine waveform limiting the power output If the short circuit or over current situation continues for more than a few seconds the inverter will turn off the AC output and...

Страница 18: ...ESCRIPTION OF TEST Temperature and Altitude 4 Category F2 Y Temperature Variation 5 Category S2 Humidity 6 Category B Operational Shock and Crash Safety 7 Category B Vibration 8 Fixed Wing Category R Curve C C1 Rotorcraft Category U Curve G Explosion 9 Category X Waterproofness 10 Category X Fluids 11 Category X Sand and Dust 12 Category X Fungus 13 Category F Salt Spray 14 Category X Magnetic Eff...

Отзывы: