6
Commissioning
18
Operating manual TROX TNC-EASYCONTROL
Fire alarm (FEuEr) for fire damper bS1…bS6
FeuErbS1 'FeuErbS2' 'FeuErbS3' 'FeuErbS4' 'FeuErbS5'
'FeuErbS6'
The closing of a fire damper that should in fact open (FD
OPEN) indicates a fire (thermal release). All fire dampers
close, the triggering fire damper is displayed, output 'Q8
Alarm 1' is switched off, 'Q11 Fire' is switched on.
Any fire alarm remains saved (failsafe) and has to be reset
on the operating menu 'rESEt'.
Fire damper functional test 'bS tESt'
If you select this item and press button S5→, the test run for
all connected fire dampers starts. Use buttons S3↑ and S4
↓
in the menu to select an item. Activate the function with S5.
Language 'Deu / En9 / Suo'
Language selection German - English - Finnish. Use buttons
S3↑ and S4↓ in the menu to select an item. Activate the
function with S5.
'xxxx'
Displays the number of functional tests. Use buttons S3↑
and S4↓ in the menu to select an item.
'xxxxx SW'
The application software version is displayed. Use buttons
S3↑ and S4↓ in the menu to select an item.
'EXIt'
Note: Closing the menu using 'EXIt' requires that all fire
dampers are OPEN.
Use buttons S3↑ and S4↓ in the menu to select an item.
Activate the function with S5.
IMPORTANT
In case of a 4-wire connection, 24 V DC are supplied
to the limit switches only when the fire damper is
open or opened (outputs Q0…Q5 are set).
Error position, switch S2 (rotary switch) 'ErrorS2'
If the rotary switch is in position S2 =0 or >6, 'Q10 Sys error'
is set. The number of connected fire dampers 1…6 has not
been correctly set.
Controlling the operating menu
Releasing the operating menu
To access the operating menu, keep buttons S3↑ and S4↓
on the PCB pressed for 2 seconds. 'rESEt' will be displayed.
Use buttons S3↑ and S4↓ in the menu to select an item.
Activate the function with S5.
Reset 'rESEt'
Use this menu item to reset the system after a fire alarm or
any other error. After resetting the system, the initialisation
process starts again, i.e. all fire dampers OPEN. Use
buttons S3↑ and S4↓ in the menu to select an item. Activate
the function with S5.
Manual control of a fire damper 'bS OPEN.. / bS
CLOSED..'
Here you can manually open or close any connected fire
dampers (according to the I/O list). Terminal connections
start with FD1! Use buttons S3↑ and S4↓ in the menu to
select an item. Activate the function with S5.