Trox Technik TNC-EASYCONTROL Скачать руководство пользователя страница 17

6

 

Commissioning

 

Operating manual TROX TNC-EASYCONTROL

 

17

 

 

 

 

Operating status menu on the PCB display

 

 

The LC display on the PCB is used to display status 

information and operating values. Buttons S3, S4 and S5 
are used for menu control.

 

switched, output 'Q9 Alarm2' is switched off, and output 

'Q10 Sys error' and output 'Q15 Functional test error' are set. 
The next functional test is only possible after reset.

 

 

Smoke detection

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Normal operation

 

 

During normal operation 'bS OK' is displayed.

 

 

Preselection

 

 

Preselecting fire dampers (FD1 to FD6)

 

Use button S2 

to select the number of connected fire 

dampers (FD 1 to FD 6). The selected value will be set once 
you switch on the control (power on). Subsequent changes 
using S2 will not affect the control. If you enter a wrong value,

 

e.g. S2 = 0 or >6, error message 'ErrorS2' will be displayed, 
and 'Q10 Sys error' will be set. Connect the dampers 
according to the wiring diagram in ascending order, starting 
with FD1 (FD1, FD2…FD6).

 

 

Initialisation

 

 

During initialisation, e.g. after switching on the control, 'bS 

Init' is displayed. 'bS Init' remains displayed until all fire 
dampers are open. After about 145 s, 'bS OK' is displayed. 
During initialisation, output 'Q6 Initialisation active' is set.   
The system is released 10 s after all fire dampers have been 
opened. Output 'Q12 No fire damper is closed' is switched. 
During this phase no operation is possible using the display. 
During initialisation, the running time for opening the fire 
damper is being monitored. If a fire damper fails to open 
within the set period of time, this fire damper is closed, and a 
message is displayed. Output 'Q12 No fire damper is closed' 
remains switched off, and output 'Q9 Alarm 2' is switched off.

 

 

Functional test / monitoring of the running time

 

 

The functional test for the fire dampers is started on input I14

 

(positive edge ↑ ), either by pressing a button or due to a

 

signal from a higher-level system. During the test, 'bS tESt' 
is displayed, and output 'Q14 Functional test is active' is set. 
Output 'Q12 No fire damper is closed' is switched off. The 
functional test is interrupted only in the event of a fire (fire 
damper closes) or when smoke is detected and signalled to 
input 'I12 SD 1 Smoke'. The closure time (25 s) and opening 
time (145 s) for the fire damper is monitored also during the 
functional test. If a fire damper fails to open or close during 
the set period of time, the fire damper is closed and 
displayed. Output 'Q12 No fire damper is closed' is not

 

If smoke is detected and signalled to input 'I12 RM 1 smoke', 

the message 'rAuch' is displayed, all fire dampers close, 'Q8 
Alarm 1' is switched off, and 'Q13 Smoke' is set. If the duct 
smoke detector is contaminated, signal at input 'I13 RM 1 
Contamination', the message 'SchmutZ' is displayed,

 

'Q10 Sys error' is set, and 'Q9 Alarm 2' is switched off.

 

 

Error messages

 

 

The following error messages may be displayed:

 

Error when opening (FEauF) fire damper bS1…bS6, running 

time error during initialisation and functional testing. 
'FeaufbS1' 'FeaufbS2' 'FeaufbS3' 'FeaufbS4' 'FeaufbS5' 
'FeaufbS6'. If during initialisation or functional testing a fire 
damper fails to open within 145 s, the fire damper is closed, 
an error message is displayed, and output 'Q9 Alarm 2' is 
switched off.

 

Error when closing (FE Zu) fire damper bS1…bS6, running 

time error 'FE ZubS1' 'FE ZubS2' 'FE ZubS3' 'FE ZubS4' 'FE 
ZubS5' 'FE ZubS6'

 

If during functional testing a fire damper fails to close within 
25 s, the fire damper is closed, an error message is 
displayed, and output 'Q9 Alarm 2' is switched off.

 

Содержание TNC-EASYCONTROL

Страница 1: ...Operating and installation manual TNC EASYCONTROL...

Страница 2: ...damper actuator connection 8 6 Commissioning 9 Standard mode 9 Parallel operation 11 TNC LINKBOX as a distribution box 11 Input and output signals 13 GST connector assembly information 16 Operating st...

Страница 3: ...y liability for any malfunction or damage resulting from non compliance with this manual or non compliance with relevant statutory regulations Other applicable documentation In addition to this instal...

Страница 4: ...ally explosive atmospheres Residual risks Danger of electric shock Do not touch any live components Electrical equipment carries a dangerous electrical voltage Only skilled qualified electricians are...

Страница 5: ...t using timer or external control by central BMS and manual triggering Output of alarm messages fire smoke fire damper closed fault during function test running limit switch faults smoke detector cont...

Страница 6: ...ce point GND Display LED yellow Input voltage V 24 V DC nominal Input current mA typ 10 Activation level high V 15 30 DC Deactivation level low V 0 5 5 DC Outputs OUT 0 OUT 15 Number of outputs 16 2 8...

Страница 7: ...ctive wrapping until just before installation Storage If you need to store the controller temporarily make sure that the following conditions apply Leave the unit in its packaging and do not expose it...

Страница 8: ...m min 8 mm Connection diameter max 2 5 mm min 0 75 mm Connections per pole 1 Fire damper actuator connection TNC EASYCONTROL can be used to control and monitor up to six motorised fire dampers If two...

Страница 9: ...able with better behaviour in the event of a fire free of halogens Duct smoke detector RM O D Fire damper with factory mounted TNC LINKBOX Easy and quick connection of actuator cables to TNC EASYCONTR...

Страница 10: ...f you do not use the TNC LINKBOX for easy and quick wiring conventional wiring with a junction box is also possible In this case wiring should be as follows External wiring of a fire damper standard o...

Страница 11: ...l operation up to 12 fire dampers It is possible to use the TNC LINKBOX also for the parallel operation of two motorised fire dampers In this case the TNC LINKBOX acts as a distribution box This confi...

Страница 12: ...GND 2 Q0 5 24V 3 I 0 2 4 6 8 10 Closed 4 I 1 3 5 7 9 11 OPEN Connection data max 10 5 mm Cable diameter Connection diameter at least 6 5 mm max 2 5 mm min 0 75 mm Connections per pole 1 If you do not...

Страница 13: ...smoke fire fire damper is closed 3 Q9 Alarm2 Signal for errors in the functional test running time and end position error smoke detector contamination 4 Q12 No fire damper is closed The connection for...

Страница 14: ...VS D sends a contamination signal NO contact an alarm is generated output Q9 This alarm is a warning and is generated when the contamination level is 70 All re dampers remain open Connecting display T...

Страница 15: ...for FD6 ncc I11 Fire damper6 OPEN Limit switch for FD6 noc I12 SD 1 Smoke SD switch ncc I13 SD 1 Contamination SD switch noc I14 Start of functional test Functional test noc I15 External release Relea...

Страница 16: ...Ith one exception Black and white connectors have the same coding According to the local regulations for health and safety at work and general safety regulations lockable plugs have to be used GST dis...

Страница 17: ...tched off and output Q9 Alarm 2 is switched off Functional test monitoring of the running time The functional test for the fire dampers is started on input I14 positive edge either by pressing a butto...

Страница 18: ...nu using EXIt requires that all fire dampers are OPEN Use buttons S3 and S4 in the menu to select an item Activate the function with S5 IMPORTANT In case of a 4 wire connection 24 V DC are supplied to...

Страница 19: ...amper OPEN yellow fire damper actuator is running red fire damper CLOSED error Function bar LED green Display OK red error Function buttons Cursor up down left right Function buttons The symbols in th...

Страница 20: ...n left right IP protection level IP 67 when installed in the front panel of the casing otherwise IP 65 Operating temperature C 20 70 Supply voltage V 8 32 DC Current consumption mA 70 at 24VDC CAN int...

Страница 21: ...the control The connected fire dampers open Duration about 170 s displayed in yellow System OK The connected fire dampers are open displayed in green Menu change with with F button below Enter the pa...

Страница 22: ...TNC EASYCONTROL Manual control of the fire damper Manual mode preselection using the function button below Manual control Select fire damper with Open fire damper with Close fire damper with Menu cha...

Страница 23: ...the functional button below Menu change with Start test with the functional button below Counter reset set test cycle counter to 0 using the function button below Test is active Duration about 170 s d...

Страница 24: ...the function button below System error Duct smoke detector is contaminated Fire damper running time error or limit switch error affected fire damper is displayed in red Check rotary switch S2 Acknowle...

Страница 25: ...to damage to property additional safety measures must be installed to prevent this Cleaning Use only mild non scouring cleaning agents Never use aggressive cleaners such as solvents or benzine Mainten...

Страница 26: ...and 4 FD2 are the inputs for the position signals Note Counting is from the right to the left 24 V DC must be supplied to the inputs of TNC EASYCONTROL hence the limit switches must also be supplied w...

Страница 27: ...to C Select the language German or English using the function button below Fire alarm The contact has been interrupted thermal release of the fire damper Acknowledgement reset with the function button...

Страница 28: ...X TNC EASYCONTROL 6 Inbetriebnahme TROX GmbH Heinrich Trox Platz D 47504Neukirchen Vluyn Telefon 49 0 28 45 2 02 0 Telefax 49 0 28 45 2 02 2 65 E Mail trox trox de www trox de Subject to change All ri...

Отзывы: