6
Commissioning
12
Operating manual TROX TNC-EASYCONTROL
Insert the plugs of the control cables for the actuators into
the connection sockets.
Connect the actuator cable to TNC-EASYCONTROL
Terminals
Box and plug
Connection
using a GST18i5 plug.
1.
0V / GND
2.
Q0…5 / 24V
3.
I 0,2,4,6,8,10 / Closed
4.
I 1,3,5,7,9,11 / OPEN
Connection data
max. 10.5 mm
Cable diameter
Connection diameter
at least 6.5 mm
max. 2.5 mm²
min. 0.75 mm²
Connections per pole
1
If you do not use the TNC-LINKBOX for easy and quick
wiring, conventional wiring with a junction box is also
possible. In this case wiring should be as follows:
External wiring of a fire damper
(standard operation)
Illustration shows fire damper
'power off to close'