 WARNING!

Explosion hazard due to incorrect
installation.

If the electrical connection between the
filter frame and the earthed system com-
ponent is not correct, electrostatic
charges could lead to an explosion.

Make sure that the terminal connec-
tion cannot come loose.

Check the electrical resistance
between the filter frame and the
system component with an ohm-
meter. The electrical resistance must
not exceed 1 MΩ (mega ohms).

5.

Finally, affix the supplied ATEX sticker to the
outside of the filter inspection access so that
people can see it.

Filter change, inserting filters

 

PFG-Ex Explosion-proof pocket filter

4

Содержание PFG-E Series

Страница 1: ...ment group 2014 34 EU II Equipment category 2014 34 EU 2 Hazardous areas 1999 92 EC Zones 1 2 21 22 Other procedural instructions and documents related to areas with potentially explosive atmos pheres as defined in directive 1999 92 EC as well as the industry specific guidelines for use handling maintenance and disposal of air filters for ventilation and air conditioning systems SWKI 2003 and VDI ...

Страница 2: ... transport damage and complete ness Then put the product back into its packaging Supply package Filter PFG Ex Earth cable ATEX label Installation and maintenance manual Transport Do not remove the protective wrapping until just before installation Storage Please note Store the product only in its original packaging Protect the product from the effects of weather Protect the product from humidity d...

Страница 3: ...aged or incomplete filter Installation Personnel Properly trained person Protective equipment Industrial safety helmet Light respiratory protection Protective gloves Before you start changing filters switch off the ven tilation and air conditioning system if necessary purge the system with fresh air beforehand 1 Remove the existing filter and the earth cable 2 Then clean the system as required 3 I...

Страница 4: ...ion Make sure that the terminal connec tion cannot come loose Check the electrical resistance between the filter frame and the system component with an ohm meter The electrical resistance must not exceed 1 MΩ mega ohms 5 Finally affix the supplied ATEX sticker to the outside of the filter inspection access so that people can see it Filter change inserting filters PFG Ex Explosion proof pocket filt...

Страница 5: ...erential pressure has been reached if this is more economic Disposal ENVIRONMENT Risk of harm to the environment due to the incor rect handling of hazardous materials and sub stances Filters and cleaning materials that have been contaminated with bacterial toxic or radioactive particles are considered hazardous waste and have to be disposed of by an authorised business in compliance with local reg...

Отзывы: