Maintenance

Explosion-proof filters are based on the same tech-
nology as conventional filters, and they work in the
same way as conventional filters of the same type
and construction

Maintenance applies mainly to the filter element.
Check the filter regularly and replace it, if neces-
sary.

The service life of a filter depends mainly on how
contaminated the air is. Check the filter in intervals
that are short enough so that you can anticipate any
defects or problems before they actually occur.

Replace the filter immediately if any of the following
is true:

the filter is defective

there are hygiene problems (micro-organisms,
fungal spores, odours, etc.)

the maximum filter usage time has been
reached (VDI 3803, part 4)

the defined final differential pressure has been
reached

For more recommendations regarding the max-
imum usage time see SWKI 2003-5, VDI 6022,
VDI 3803 and EN 13053.

You may replace a filter even before the defined
final differential pressure has been reached if this
is more economic.

Disposal

 ENVIRONMENT!

Risk of harm to the environment due to the incor-
rect handling of hazardous materials and sub-
stances.

Filters and cleaning materials that have been
contaminated with bacterial, toxic or radioactive
particles are considered hazardous waste and
have to be disposed of by an authorised business
in compliance with local regulations.

Disposing of filter elements with household waste is
allowed only in the following cases:

For unused filter elements

For filter elements that have been exposed
only to atmospheric outdoor air

Ordering replacement filters

To ensure permanent protection from particulate
matter and other pollutants we recommend using
only original TROX filters.

Original TROX filters carry a sticker on the frame
with information on how to order replacements.

To avoid downtime of the ventilation and air con-
ditioning system, we recommend you to always
have the required filters in stock.

To order replacement filters:

https://www.trox.de/onlineshop/filtergeraete-und-
filterelemente-1df986693c21980d

Maintenance

 

PFG-Ex Explosion-proof pocket filter

5

Содержание PFG-E Series

Страница 1: ...ment group 2014 34 EU II Equipment category 2014 34 EU 2 Hazardous areas 1999 92 EC Zones 1 2 21 22 Other procedural instructions and documents related to areas with potentially explosive atmos pheres as defined in directive 1999 92 EC as well as the industry specific guidelines for use handling maintenance and disposal of air filters for ventilation and air conditioning systems SWKI 2003 and VDI ...

Страница 2: ... transport damage and complete ness Then put the product back into its packaging Supply package Filter PFG Ex Earth cable ATEX label Installation and maintenance manual Transport Do not remove the protective wrapping until just before installation Storage Please note Store the product only in its original packaging Protect the product from the effects of weather Protect the product from humidity d...

Страница 3: ...aged or incomplete filter Installation Personnel Properly trained person Protective equipment Industrial safety helmet Light respiratory protection Protective gloves Before you start changing filters switch off the ven tilation and air conditioning system if necessary purge the system with fresh air beforehand 1 Remove the existing filter and the earth cable 2 Then clean the system as required 3 I...

Страница 4: ...ion Make sure that the terminal connec tion cannot come loose Check the electrical resistance between the filter frame and the system component with an ohm meter The electrical resistance must not exceed 1 MΩ mega ohms 5 Finally affix the supplied ATEX sticker to the outside of the filter inspection access so that people can see it Filter change inserting filters PFG Ex Explosion proof pocket filt...

Страница 5: ...erential pressure has been reached if this is more economic Disposal ENVIRONMENT Risk of harm to the environment due to the incor rect handling of hazardous materials and sub stances Filters and cleaning materials that have been contaminated with bacterial toxic or radioactive particles are considered hazardous waste and have to be disposed of by an authorised business in compliance with local reg...

Отзывы: