> 100 mm distance to load-bearing structural elements, ≥ 75 mm on side B (depending on construction).
≥ 200 mm distance between two fire dampers
1.
Create an installation opening with H + 88 mm and B + 88 mm.
2.
Ensure that the two perimeter seals and the sealing strips are intact. If any of the seals has been damaged, do
not install the fire damper.
3.
Remove the sealing strip fixing screws that were used during transport ( Fig. 5 /4).
4.
Push the fire damper into the installation opening and secure it. Ensure that the installation subframe rests on
the face of the wall and that the sealing strips provide complete sealing between the subframe and the wall.
5.
Screw-fix the fire damper with anchors and M8 screws, or with M8 fixing tabs ( Fig. 5 /7).
Use only fire-rated screw fixing systems with suitability certificate, e.g. Hilti M8
×
95/30 anchors or equivalent.
Installation
Solid walls > Dry mortarless installation
Tunnel fire damper Type FKT-EU
15