5.4 Solid walls
5.4.1 Dry mortarless installation
Fig. 5: Installation into a solid wall
①
FKT-EU fire damper
②
Installation subframe
③
Sealing strips
④
Fixing screws for sealing strips (during transport)
⑤
Intumescent seal
⑥
Solid wall
⑦
Screw fix connection
Ⓐ
Installation side, exposed side (i)
Ⓑ
Operating side, non-exposed side (o)
Installation after completing the wall
Personnel:
Specialist personnel
Requirements
Performance class EI 120 S
Solid walls or compartment walls made of, for example, concrete, aerated concrete or masonry, gross density
≥ 2300 kg/m³ and W ≥ 250 mm
Installation
Solid walls > Dry mortarless installation
Tunnel fire damper Type FKT-EU
14
Содержание FKT-EU
Страница 26: ...Tunnel fire damper Type FKT EU 26...
Страница 27: ...Tunnel fire damper Type FKT EU 27...