Connecting cable for the control panel
TCU3 or TAM
Installation to a wall or to furniture
How to proceed
1.Create a cut-out and drill any necessary holes
into the wall.
2.Lay the cable for the connection of the control
panel with the controller. Take the control panel
end of the cable and pull it from the wall for about
10 cm.
3.Carefully remove the control panel base plate:
The release openings are located on the left side
of the casing. Fix the base plate.
4.Put the plug of the connecting cable into the
socket of the control panel such that it locks into
place. → See picture to the right.
5.Align the control panel including the cable with
the base plate and press it back onto the base
plate until it locks into place. In the process,
carefully push the connecting cable back into
the wall without kinking it.
Connection to the control panel
The socket for the connecting cable is on the rear of
the control panel.
Connection to the controller
Connect the control panel cable to either Terminal 1
(X2) or Terminal 2 (X3).
The remaining connection is intended for a second
control panel.
The control panel can only be used when it has
been configured on a TCU3 controller or TAM with
active room management function.
23
BE-LCD-01 Operating and Installation Manual / Leaflet no. M375EV8 (01/2015)
6 Installation and electrical wiring
Base plate
Wall
Connecting
cable