Installation
Personnel:
HVAC technician
Protective equipment:
Protective gloves
Safety shoes
Industrial safety helmet
Only specialist personnel are allowed to perform the
described work on the VAV terminal unit.
Only skilled qualified electricians are allowed to work on
the electrical system.
CAUTION!
Danger of injury from sharp edges and sheet
metal parts.
–
Always wear protective gloves when handling the
unit.
The control component is delivered mounted on the VAV
terminal unit so that the work is limited to the electrical
wiring
and to the setting of
When installing the VAV terminal unit, take particular
note of the following points:
Upstream section
–
A special upstream flow length is not required
for the TVE terminal unit.
Direction of airflow
–
For TVE terminal units with control component
XS0, the direction airflow is clearly specified (air-
flow direction arrow).
–
For TVE terminal units with control component
XM0, a preferred airflow direction is specified
(acoustic), alternative installation possible.
Fixing/suspension
Accessibility for service work
Information on this can be found in the VAV terminal unit
installation and commissioning instructions.
Installation orientation
Any installation orientation of the VAV terminal unit is
possible for both the XM0 (transducer with dynamic
measuring principle) and the XS0 (transducer with static
measuring principle). The terminal unit may be mounted
in such a way that the position of the control component
is above, below or to the side of the duct.
Installation
Control component Compact XM0 • XS0 for VAV terminal unit TVE