10          TX3706-UM-EN-02

3.  Fitting and Installation

3.1 Precautions

  Special conditions of use relating to the Ex 

certification may apply to particular applications.

•  The cable gland used with Free Plugs and Free 

Receptacles must be an approved Ex d type 

which is suitably certified for the equipment and 

the type of cable to be used.

• 

Gland entries must be fitted with suitable ingress 

seals to maintain the overall ingress protection of 

the connector.

•  Ensure that the current and voltage parameters 

of the electrical circuits are within the limits 

specified.

•  The sealing faces and flame paths will have 

been treated with a protective film of grease 

during manufacture. Renew if necessary before 

assembly or engagement, in accordance with the 

relevant installation standards and procedures.

•  Ensure that the end cap screws are in place and 

are fully tightened before engagement.

•  Always fit either a rubber ingress protection cap 

or an Ex protection cap to disengaged connectors 

to protect flame paths and to exclude debris and 

moisture. 

• 

Do not disengage the connector by pulling on the 

cable as this may damage the fitting of the cable 

into the cable gland.

•  A connector with a damaged flame path is an 

explosion risk and should be removed from 
service.

www.trolex.com

Содержание TX3706

Страница 1: ......

Страница 2: ......

Страница 3: ...nd Equipment 11 3 3 Free Plug and Free Receptacle 11 3 3 1 General assembly definitions 11 3 3 2 Connecting 12 3 3 3 Earth bonding 14 3 3 4 Security coding 14 3 4 Fixed Receptacle 15 3 4 1 General ass...

Страница 4: ...no special tools required Double insulated contact cartridge for added safety and ease of connection Rapid double bayonet engagement ensures that contacts make or break under Ex d protection for live...

Страница 5: ...nect disconnect of control circuits and power circuits for electrical equipment installation Live disconnect of critical equipment for maintenance and change out Offshore oil and gas platforms mining...

Страница 6: ...ycles 100 000 with no load connected Limited to 200 for live disconnect Security Coding 5 selectable coding positions A B C D E Ingress protection IP66 Temperature limits 50 C to 60 C Weight Free Plug...

Страница 7: ...94 V 0 Contacts Multi spring wire socket and solid pin Insertion force 6 N per contact Contact protection Passivated silver plating Contact resistance 400 ohm Test Voltage 2000 V Insulation Class II d...

Страница 8: ...19 01 xx xx xx xx TX3706 4 19 01 CML 15ATEX1143X IECEx CML 15 0070X I M2 Ex db I Mb 50 C Ta 60 C 2 Fixed Receptacle low risk of mechanical danger only refer to conditions of use below Product Code Ex...

Страница 9: ...arrangement remains flameproof through the first stage of disconnection which fully disconnects the pins however this only applies to circuits with a power factor of between 0 6 and 1 0 For circuits o...

Страница 10: ...in the limits specified The sealing faces and flame paths will have been treated with a protective film of grease during manufacture Renew if necessary before assembly or engagement in accordance with...

Страница 11: ...way 4 way 5 Backing ring 6 Contacts 1 5 mm2 Pins Sockets 2 5 mm2 Pins Sockets 7 Retainer 8 Sleeve Upper and lower pair 9 Ingress protection cap 10 Earth bonding terminal 11 Flame path 12 Cable entry...

Страница 12: ...FEMALE contact inserts MALE or FEMALE contact inserts can be fitted into PLUGS or RECEPTACLES Checkpoint Use sleeve 8 as a temporary wire length cutting gauge 1 4 6 7 5 8 10 2 12 3 8 2 Standard Ex cab...

Страница 13: ...5 Clip a retaining clip 7 to each contact Load contacts into the contact insert 4 Slide the backing ring 5 up to the contact insert 4 Clip the sleeves 8 in place Load into connector body 1 Fit end ca...

Страница 14: ...rth bonding Internal Earth Continuity bonding 3 3 4 Security Coding Female Male 2 5mm2 1 10 2 Leading Earth Pin TX 3706 031 15 TX 3706 031 25 6 4 5 8 2 E D C B A 8 8 E D C B A Code B E D C B A Pull Pu...

Страница 15: ...sh M20 M25 3 Locking ring with ingress seals 4 Ingress seal for surface mounting 5 Ingress protection cap 6 Pre wired encapsulated connections 1 5 mm2 X 1M 2M 3M L 2 5 mm2 X 1M 2M 3M L 7 Female contac...

Страница 16: ...ure 3 Use a half spanner to apply counter clockwise locking force to the locking ring A locking ring enables the Receptacle to be radially positioned to suit user preference and incorporates ingress s...

Страница 17: ...X3706 UM EN 02 17 TX3706 User Manual 4 Operation 4 1 Engage and separate Locking Screw Line Receptacle TX3706 2 Fixed Receptacle TX3706 3 Line Plug TX3706 1 The locking screw must be tightened to comp...

Страница 18: ...ing upon the application and local safety regulations 4 2 1Isolate elsewhere Isolate all electrical power at source BEFORE separation Checkpoint IP65 Ex d IP66 Fit the rubber ingress protection cap wh...

Страница 19: ...32 25 Engage Ex d Protection Break Ex d Protection Separate IP65 Ex d IP66 Fit the rubber ingress protection cap when separated Fit an Ex protection cap if the system power is to be reinstated Checkpo...

Страница 20: ...d Protection Break Ex d Protection Separate IP30 on Socket Checkpoint Maximum Voltage 4 way 250 V ac dc Maximum Voltage 10 way 80 V ac Maximum breaking current per contact 1 A Power factor Between 0 6...

Страница 21: ...o longer Ex d or Ex tb protected however creepage and clearances of the connector meet requirements of IEC EN 60079 7 for the maximum rated live disconnection voltages Fitting Ex protection cap restor...

Страница 22: ...2 5 mm2 P5609 16 01 Live disconnect pilot pin 1 5 mm2 P5609 23 02 Maximum current 1 Amp Live disconnect pilot pin 2 5 mm2 P5609 16 02 Maximum current 1 Amp Ex protection plug cap Aluminium TX3706 41 S...

Страница 23: ...ntained herein If you have any suggestions for improvements or amendments or find errors in this publication please notify us at marketing trolex com No part of this document may be reproduced in any...

Страница 24: ......

Страница 25: ......

Страница 26: ......

Отзывы: