16 P5629.1600 Rev A
• The Modbus slave Min and Max sets the TCP slave address limits for that port.
• Packet Timeout sets the maximum time waiting for the first byte of a reply from
a slave. (100ms is typical but may be extended for “slow” slaves or reduced for
“fast” ones)
• Byte Timeout determines the end of a slaves reply as when another byte is not
received during this time. (typically set between 2ms and 20ms depending upon
Baudrate)
• Poll Delay slows down the packet rate if required. (Default is 0ms)
• RTS ON Delay gives a delay after RTS before the packet data is sent, RTS OFF
gives a delay after the packet data is sent before releasing RTS signal (typically
0ms to 5ms)
• Once the settings have been configured click the submit button.
• Configuration message will be displayed for 3 seconds before returning back to the
main page.
• Click on the Diagnostics page option and it will display the following screen.
• This page shows the counters for all of the LAN connected Modbus/TCP clients as
well as the serial ports, this can be useful for fault finding.