Manual mixer shower

3

PLUMBING REQUIREMENTS

DO NOT

 use jointing compounds on any pipe 

fittings for the installation.

DO NOT

 solder fittings near the mixer unit 

as heat can transfer along the pipework and 
damage the mixer valve.

IMPORTANT:

 

•  The layout and sizing of pipework MUST 

be such that nominally equal inlet supply 
pressures are achieved and the effects of 
other draw-offs are minimised.

•  The pipework should be installed such 

that other taps and appliances being 
operated elsewhere on the premises do not 
significantly affect the flow

•  When connecting pipework avoid using tight 

90° elbows; swept or formed bends will give 
the best performance.

•  The hot water pipe entry must be made to 

the left-hand side inlet, marked HOT, ‘H’ or 
with a red/orange label.

•  Suitable isolating valves (complying with 

Water Regulations and Bylaws) must be fitted 
on the hot and cold water supplies to the 
shower as an independent means of isolating 
the water supplies should maintenance 
or servicing be necessary. If this isolator is 
fitted in a loft space, the loft must have a 
fixed access ladder and be boarded, with 
appropriate lighting from the access point to 
the isolator.

•  It is preferable to flush the pipework to clear 

the system of debris and check for leaks 
before connecting to the mixer.

Commercial applications

•  Triton recommends for all commercial 

applications that, easily accessible, in-line 
filters are used to aid maintenance.

Hard water areas

a.  If it is intended to operate the shower 

in areas of hard water (above 200-ppm 
temporary hardness), a scale inhibitor may 
have to be fitted. For advice on the Triton 
scale inhibitor, please contact Customer 
Service.

b.  For best performance the showerhead MUST be 

regularly cleaned to remove scale and debris.

WATER SYSTEM REQUIREMENTS

This mixer shower is suitable for:

•  Gravity water systems
•  Pumped gravity systems
•  Fully modulating type combination boilers
•  Multi-point hot water heaters
•  Thermal storage
•  Unvented systems
When installing this mixer with a combination or 
multi-point boiler, it may be necessary to install 
flow regulation. 
Check that the appliance is capable of delivering 
hot water at a minimum switch-on flow rate 
of 3 litres per minute. At flow rates between 3 
and 8 litres per minute, the appliance must be 
capable of raising the water temperature to 52°C 
minimum. 
Water temperature at the inlet of the mixer valve 
must remain relatively constant when flow rate 
adjustments are made. Refer to the appliance 
operating manual to confirm compatibility with 
this mixer shower.
Where thermal store systems and instantaneous 
gas water heaters are used, if excessive draw-
off takes place, the appliance may not be able 
to maintain an adequate output temperature. 
This could result in the shower temperature 
becoming noticeably cooler.
The hot supply temperature MUST remain a 
minimum of 10°C hotter than the required blend 
temperature for optimum performance.

Содержание Kaho

Страница 1: ...se note these instructions are to be left with the user CAUTION THIS PRODUCT IS NOT THERMOSTATICALLY CONTROLLED The showerhead and hose supplied with this product are an integral part of the safety of...

Страница 2: ...N COMPONENTS 1 INTRODUCTION 2 SITE REQUIREMENTS 2 SAFETY WARNINGS 2 PLUMBING REQUIREMENTS 3 WATER SYSTEM REQUIREMENTS 3 TYPICAL SUITABLE INSTALLATIONS 4 5 SITING OF THE SHOWER 6 FITTING THE MIXER 7 BO...

Страница 3: ...ixing plinth 4 Outlet adaptor 5 Blanking plug 6 Elbows and fittings X2 7 Olive nut trim X2 All dimensions listed in this fitting book regarding the product and installation are approximate All kits an...

Страница 4: ...e must not be exceeded Pressure reducing valve On sites where the running pressure is above 5 bar the use of a suitably sized pressure reducing valve fitted in the cold mains supply pipework can provi...

Страница 5: ...ns that easily accessible in line filters are used to aid maintenance Hard water areas a If it is intended to operate the shower in areas of hard water above 200 ppm temporary hardness a scale inhibit...

Страница 6: ...with an unvented stored hot water cylinder For systems with no cold water take off after the appliance reducing valve it will be necessary to fit an additional drop tight pressure reducing valve when...

Страница 7: ...mal store manufacturer Gravity fed systems fig 5 The shower control MUST be fed from a cold water cistern and hot water cylinder providing nominally equal pressures There MUST be a minimum of one metr...

Страница 8: ...ies showerhead riser rail can be positioned above or to either side of the shower refer to fig 6 Supply pipework Complete the pipework to the shower area having decided on the position of the shower a...

Страница 9: ...mounting plate onto the wall fig 8 The inlet elbows allow for either rising falling or rear entry hot and cold water supplies The elbow adapters have two O ring seals fig 9 to the body and do not requ...

Страница 10: ...all compression fittings Tighten all the grub screws to secure the mixer to mounting plate FITTING THE CONTROL LEVER Push the control lever onto the valve Using an Allen key secure the lever to the va...

Страница 11: ...t the water temperature turn the control lever clockwise for a hotter shower and anti clockwise for a cooler shower fig 15 To stop the shower To start the shower Anti clockwise for cooler Clockwise fo...

Страница 12: ...wer head connected Important Product flow rates are for guidance only CLEANING DO NOT use abrasive or solvent cleaning fluids The shower unit riser rail hose etc should be cleaned using a soft cloth a...

Страница 13: ...Manual mixer shower 11 All dimensions listed in this fitting book regarding the product and installation are approximate DIMENSIONS 100mm 130mm 150mm 1 2 BSP...

Страница 14: ...enuine Triton spare part for your product please visit www tritonshowers co uk spares for product codes and prices Alternatively please call our Customer Services team on 024 7637 2222 to order direct...

Страница 15: ...4 1 Reduce the simultaneous demand from the mains supply 2 1 1 Turn the control lever clockwise 2 2 1 Turn the control lever clockwise 2 3 1 Make sure heating appliance is set to maximum or has suffi...

Страница 16: ...or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please...

Отзывы: