background image

Manual mixer shower

2

Replacement parts can be ordered from Triton Customer 
Service. See 

‘spare parts’

 for details.

INTRODUCTION

This book contains all the necessary fitting and 
operating instructions for your Triton mixer 
shower. Please read them carefully and read 
through the whole of this book before beginning 
your installation.
The shower installation must be carried out by 
a suitably competent person and in sequence of 
this instruction book.
Care taken during the installation will give a long 
and trouble free life from your mixer shower.

SITE REQUIREMENTS

The installation must be in accordance with 
Water Regulations and Bylaws.

Water pressure requirements

Running water pressure:

 Gravity fed 

-  0.1 bar min.

  

  1.0 bar max.

 Mains fed 

-  1.0 bar min.

  

  5.0 bar max.

Maximum static water pressure:

 Gravity and mains  -  10 bar

This mixer shower is designed for use with 
traditional low pressure gravity water systems, 
using a cold water cistern and hot water cylinder, 
as well as for the higher pressure systems found 
in the UK up to a maximum of 5 bar running 
pressure.
For effective operation of the internal seals, the 
maximum static pressure must not be exceeded.

Pressure reducing valve

On sites where the running pressure is above 5 
bar, the use of a suitably sized pressure reducing 
valve fitted in the cold mains supply pipework 
can provide nominally equal pressures at the 
mixer shower.

Water minimum flow rate

For best performance within the specified 
running pressure range a minimum flow of 
8 litres per minute should be available to both 
inlets.

Water temperature requirements

Maximum hot water temperature:  = 80°C

Recommended maximum: 

= 65°C

Minimum hot water temperature:  = 52°C

Maximum cold water temperature:  = 20°C

The mixer shower MUST NOT be subjected to 
water temperatures above 80°C.

BS 6700 recommends that the temperature of 
stored water should never exceed 65°C.
A stored water temperature of 60°C is considered 
sufficient to meet all normal requirements and 
will minimise the effects of scale in hard water 
areas.

SAFETY WARNINGS

a. 

DO NOT

 choose a position where the 

shower could become frozen.

b. 

DO NOT

 connect this mixer shower to any 

form of tap or fitting not recommended by 
the manufacturer.

c. 

DO NOT

 allow the inlet pressure or flow 

rates to operate outside the guidelines laid 
out in ‘site requirements’.

d.  

DO NOT

 connect the mixer shower to a 

gravity hot supply and a mains cold supply 
or vice versa.

CAUTION!

THIS PRODUCT IS NOT 

THERMOSTATICALLY CONTROLLED

Содержание Kaho

Страница 1: ...se note these instructions are to be left with the user CAUTION THIS PRODUCT IS NOT THERMOSTATICALLY CONTROLLED The showerhead and hose supplied with this product are an integral part of the safety of...

Страница 2: ...N COMPONENTS 1 INTRODUCTION 2 SITE REQUIREMENTS 2 SAFETY WARNINGS 2 PLUMBING REQUIREMENTS 3 WATER SYSTEM REQUIREMENTS 3 TYPICAL SUITABLE INSTALLATIONS 4 5 SITING OF THE SHOWER 6 FITTING THE MIXER 7 BO...

Страница 3: ...ixing plinth 4 Outlet adaptor 5 Blanking plug 6 Elbows and fittings X2 7 Olive nut trim X2 All dimensions listed in this fitting book regarding the product and installation are approximate All kits an...

Страница 4: ...e must not be exceeded Pressure reducing valve On sites where the running pressure is above 5 bar the use of a suitably sized pressure reducing valve fitted in the cold mains supply pipework can provi...

Страница 5: ...ns that easily accessible in line filters are used to aid maintenance Hard water areas a If it is intended to operate the shower in areas of hard water above 200 ppm temporary hardness a scale inhibit...

Страница 6: ...with an unvented stored hot water cylinder For systems with no cold water take off after the appliance reducing valve it will be necessary to fit an additional drop tight pressure reducing valve when...

Страница 7: ...mal store manufacturer Gravity fed systems fig 5 The shower control MUST be fed from a cold water cistern and hot water cylinder providing nominally equal pressures There MUST be a minimum of one metr...

Страница 8: ...ies showerhead riser rail can be positioned above or to either side of the shower refer to fig 6 Supply pipework Complete the pipework to the shower area having decided on the position of the shower a...

Страница 9: ...mounting plate onto the wall fig 8 The inlet elbows allow for either rising falling or rear entry hot and cold water supplies The elbow adapters have two O ring seals fig 9 to the body and do not requ...

Страница 10: ...all compression fittings Tighten all the grub screws to secure the mixer to mounting plate FITTING THE CONTROL LEVER Push the control lever onto the valve Using an Allen key secure the lever to the va...

Страница 11: ...t the water temperature turn the control lever clockwise for a hotter shower and anti clockwise for a cooler shower fig 15 To stop the shower To start the shower Anti clockwise for cooler Clockwise fo...

Страница 12: ...wer head connected Important Product flow rates are for guidance only CLEANING DO NOT use abrasive or solvent cleaning fluids The shower unit riser rail hose etc should be cleaned using a soft cloth a...

Страница 13: ...Manual mixer shower 11 All dimensions listed in this fitting book regarding the product and installation are approximate DIMENSIONS 100mm 130mm 150mm 1 2 BSP...

Страница 14: ...enuine Triton spare part for your product please visit www tritonshowers co uk spares for product codes and prices Alternatively please call our Customer Services team on 024 7637 2222 to order direct...

Страница 15: ...4 1 Reduce the simultaneous demand from the mains supply 2 1 1 Turn the control lever clockwise 2 2 1 Turn the control lever clockwise 2 3 1 Make sure heating appliance is set to maximum or has suffi...

Страница 16: ...or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please...

Отзывы: