background image

5

Manual Bypass Operation (for UPS maintenance or replacement)

WARNING! For qualified service personnel only. Failure to follow the bypass procedure completely will not adequately power down 
the UPS, resulting in the continued risk of death or injury from potential contact with high voltage. The UPS and detachable PDU are 
extremely heavy. This procedure requires several people to perform.

The UPS system includes an independent, detachable PDU with a Maintenance Breaker Switch. This switch allows qualified service personnel 
to remove the detachable PDU from the UPS for routine maintenance without disrupting power to connected loads. While this switch is set to 
“BYPASS”, connected equipment will receive unfiltered AC mains power. But the equipment will not receive battery power in the event of a 
blackout.

UPS Removal

STEP 1. 

Disable PowerAlert and disconnect the SNMP or serial USB communication cables from the communication ports on the UPS. Do NOT 

remove the parallel cable (if installed) at this point.

STEP 2.

  First, determine your maintenance status (i.e. which UPS system requires maintenance and whether you are in Redundancy or Power 

Mode). Press UPS’s “OFF” button, if the UPS is powered, until you hear a beep and see a “BYPASS MODE” message shown in its LCD 

Display.

STEP 3.  Part A:

 When the output is coming from the Primary UPS and the Secondary UPS needs repair, set the Primary PDU’s Input/Output 

Breakers ON, the Secondary PDU’s Input/Output Breakers OFF and the Maintenance Breaker OFF.

 

Part B:

 When the output is coming from the Secondary UPS and the Primary UPS needs repair, set the Primary PDU’s Input/Output 

Breakers OFF, the Secondary PDU’s Input/Output Breakers ON and the Maintenance Breaker OFF.

 

Part C:

 When the output is in Bypass, set Maintenance Breaker Switch to the ON position. At this point, remove the parallel cable from the 

UPS.

STEP 4.

  If an external battery module is connected to the UPS, disconnect it from the UPS.

 

The UPS is now safely powered down and it can be detached from the PDU to perform maintenance/replacement.

STEP 5.

  Remove the four screws that secure the front mounting ears of your UPS to the rack. With the PDU still attached, move the UPS system 

and PDU forward in the rack slightly (approximately 4 inches), being sure that both components remain adequately supported by the UPS’s 

rackmount support rails.

STEP 6. 

At the rear of the UPS, remove the four screws that hold the detachable PDU to the UPS that is being serviced. With an assistant holding 
the front of the UPS in place, carefully detach the PDU from the rear of the UPS and rest it on the UPS support rails. Remove the UPS from 
the rack.

Output Status (normal Operation)

Primary PDU Input/Output 

Breakers

Secondary PDU Input/Output 

Breakers

Maintenance Breaker*

Output coming from both UPS systems.

ON

ON

OFF

Output Status (Redundancy Mode)

Primary PDU Input/Output 

Breakers

Secondary PDU Input/Output 

Breakers

Maintenance Breaker*

Output coming from Primary UPS. 
Secondary UPS needs  repair.  
(Refer to Step 3, Part A)

ON

OFF

OFF

Output coming from Secondary UPS. 
Primary UPS needs repair.  
(Refer to Step 3, Part B)

OFF

ON

OFF

Output Status (Power Mode)

Primary PDU Input/Output 

Breakers

Secondary PDU Input/Output 

Breakers

Maintenance Breaker*

Output coming from Bypass.  
(Refer to Step 3, Part C)

OFF

OFF

ON

*On Primary PDU only.

Note: Units will operate in Redundancy Mode up to 6kVA and switch to Power Mode at loads greater than 6kVA.

Содержание SUPDMB12KHW

Страница 1: ...y Secondary Parallel PDU Units Model SUPDMB12KHW Introduction 2 Important Safety Warnings 2 Features 3 Mounting 3 Espa ol 7 Storage and Service 6 Fran ais 13 Warranty and Warranty Registration 6 19 Co...

Страница 2: ...ous oxide Maintenance Warning Your PDU Kit does not require routine maintenance Do not open the PDUs for any reason There are no user serviceable parts inside Service and repair should be done only by...

Страница 3: ...ation see Step 1 simply attach the primary PDU module to UPS system 1 and the secondary PDU module to UPS system 2 using the provided mounting screws as shown Before installing and operating the PDU K...

Страница 4: ...to the markings on the connectors The AC input wiring attaches to the facility s AC source while the AC output wiring connects to the intended equipment Model Input Voltage Maximum Rated Input Curren...

Страница 5: ...put Output Breakers OFF the Secondary PDU s Input Output Breakers ON and the Maintenance Breaker OFF Part C When the output is in Bypass set Maintenance Breaker Switch to the ON position At this point...

Страница 6: ...t back for repair THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORT...

Страница 7: ...pp Lite Todos los derechos reservados Kit de PDU paralelo para Sistemas UPS SmartOnline 6kVA Unidades de PDU paralelos principales y secundarios Modelo SUPDMB12KHW Introducci n 8 Advertencias de segur...

Страница 8: ...uiere rutina de mantenimiento Bajo ninguna circunstancia abra el PDU No tiene partes internas que el usuario pueda reparar S lo personal capacitado debe llevar a cabo el mantenimiento y la reparaci n...

Страница 9: ...secundario al sistema UPS 2 utilizando los tornillos de montaje suministrados como se muestra en la figura Antes de instalar y hacer funcionar el kit de PDU debe familiarizarse con la ubicaci n y fun...

Страница 10: ...res El cableado de entrada de CA se conecta a la fuente de CA de la instalaci n en tanto que el cableado de salida de CA se conecta a los equipos deseados Modelo Voltaje de entrada Corriente de entrad...

Страница 11: ...PDU secundario y APAGUE el disyuntor de mantenimiento Parte C Cuando la salida est en modo de derivaci n coloque el interruptor disyuntor de mantenimiento en la posici n de ENCENDIDO En este momento...

Страница 12: ...ripp Lite 1111 W 35th Street Chicago IL 60609 EE UU El vendedor abonar los cargos de env o de devoluci n Visite www tripplite com support antes de enviar cualquier equipo para reparaci n ESTA GARANT A...

Страница 13: ...Tripp Lite Tous droits r serv s Ensemble de PDU parall le pour syst mes d ASI SmartOnline 6kVA Unit s PDU parall les principales et secondaires Mod le SUPDMB12KHW Introduction 14 Consignes de s curit...

Страница 14: ...on d entretien Ne l ouvrir sous aucun pr texte Aucune pi ce ne peut tre r par e par l utilisateur Les travaux d entretien et de r paration doivent tre effectu s uniquement par un technicien form Tous...

Страница 15: ...pal au syst me d ASI n 1 et le module de la PDU secondaire au syst me d ASI n 2 en utilisant les vis de montage fournies tel qu illustr Avant d installer et de mettre le PDU en marche familiarisez vou...

Страница 16: ...la source de CA de l installation tandis que le c blage de sortie CA se connecte l quipement voulu Mod le Tension d entr e Courant nominal d entr e maximal Courant nominal de sortie maximal Taille typ...

Страница 17: ...PDU principale sur OFF les disjoncteurs d entr e de sortie de la PDU secondaire sur ON et le disjoncteur de maintenance sur OFF Partie C Lorsque la sortie est en d rivation r glez le commutateur de d...

Страница 18: ...en payant d avance les frais d exp dition et de livraison Tripp Lite 1111 W 35th Street Chicago IL 60609 USA Le Vendeur paiera les frais de retour Visitez www tripplite com support avant de renvoyer u...

Страница 19: ...1111 W 35th Street Chicago IL 60609 USA www tripplite com support Copyright 2010 Tripp Lite SmartOnline Tripp Lite SmartOnline 6 PDU SUPDMB12KHW 20 20 21 21 English 1 24 Espa ol 7 24 Fran ais 13 22 2...

Страница 20: ...20 PDU SUPDMB 6 6 PDU SUPDMB12KHW Tripp Lite PDU PDU 0 40 C 17 29 C PDU PDU 6 6 PDU 6 6 6 12 PDU 6 6 6 12 12 50 100 50 6 6 12...

Страница 21: ...21 SU6000RT4UHVPM 6 12 6 SU6000RT4UHVPM 1 1 1 6 2 6 6 2 6 4 1 PDU 1 2 PDU PDU PDU 1 Tripp Lite 2 3 4 5 6 PDU 7 PDU 8 14 SW 14 SW 14 SW 14 SW 1 2 1 2 1 1 8 8 7 6 5 4 3 2 6 5...

Страница 22: ...22 6 PDU 1 PDU 2 B A PDU C PDU 2 3 PDU 1 2 3 4 LI L2 PDU SUPDMB12KHW 200 240 L N 60 60 8 2 5 PDU 6 7 Parallel Master Parallel Slave 8 PDU 2 3 4 5 8 V00 CV01 V00 CV01 A B C...

Страница 23: ...23 PDU PDU PDU BYPASS 1 PowerAlert SNMP USB 2 OFF BYPASS MODE 3 A PDU PDU B PDU PDU C ON 4 PDU 5 PDU 10 6 PDU PDU PDU PDU ON ON OFF PDU PDU 3 A ON OFF OFF 3 B OFF ON OFF PDU PDU 3 C OFF OFF ON 6 6...

Страница 24: ...oduct Returns RMA RMA Tripp Lite Tripp Lite 2 2 Tripp Lite 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Tripp Lite 1111 W 35th Street Chicago IL 60609 USA Tripp Lite WEEE Tripp Li...

Отзывы: