3
Mounting
The user must determine the fitness of hardware and procedures before mounting. If hardware
and procedures are not suitable for your application, contact the manufacturer of your rack or
rack enclosure. The procedures described in this manual are for common rack and rack enclosure
types and may not be appropriate for all applications.
Parallel configuration supports the mounting of two SU6000RT4UHVPM power/battery modules
for fault-tolerant redundancy that supports loads up to 6kVA, or, for increased capacity, up to
12kVA. For all 6kVA UPS system mounting instructions, please refer to that product’s Owner’s
Manual. In order to configure your UPS for redundancy, you will also need to obtain two
SU6000RT4UHVPM power/battery modules with this parallel kit.
1
It is important to note that in order to accommodate paralleling applications, the UPS systems
must be mounted in the following order (see diagram 1): 6kVA UPS system 1 and 6kVA UPS
system 2.
Note: Each 6kVA UPS system must be installed in separate rack rails before
attaching the rear parallel power distribution units.
2
Referring to the above step and the mounting instructions of the 6kVA UPS systems, mount
the two UPS systems into the 4-post rack. Once the UPS systems have been mounted in the
correct configuration (see Step 1), simply attach the primary PDU module to UPS system
1 and the secondary PDU module to UPS system 2 using the provided mounting screws as
shown.
Before installing and operating the PDU Kit, familiarize yourself with the location and function of the features of each component.
Primary Parallel PDU Module
Secondary Parallel PDU Module
Features (Rear Panel)
1
External Battery Connector:
Use this to connect one or more Tripp Lite battery modules to the power module. Remove the cover for access.
Refer to the battery module Owner’s Manual for connection instructions and safety warnings.
2
Parallel Connector:
For UPS communication in parallel.
3
Utility Input Terminal Block:
Use this terminal to connect your power module to utility power. Unscrew and remove the cover over the block
for access.
4
Equipment Output Terminal Block:
Use this terminal to connect your power module to your equipment. Unscrew and remove the cover over
the block for access.
5
AC Input Breaker:
One double-pole circuit breaker controls input power to the power module.
6
Parallel Power Interconnect:
Connects Primary and Secondary Parallel PDUs.
7
Maintenance Breaker:
Allows qualified service personnel to remove the detachable PDU from the power/battery module for routine
maintenance without disrupting power to the connected loads.
8
AC Output Breaker:
One double-pole circuit breaker controls output power to the load.
14
SW
14
SW
14
SW
14
SW
1
2
UPS System 1
UPS System 2
1
1
8
8
7
6
5
4
3
2
6
5