11. Troubleshooting
Problem
Possible Cause
Solution
Compressor will not run
while fan motor runs
(continued)
Room Temp Sensor
Check the temperature setting if not at the coolest (in cooling
mode) or warmest (in heating mode). Set it if not.
Compressor
Check the compressor for open circuit or ground. If open or
grounded, replace the compressor.
Copper tubing
Remove the cabinet and carefully rearrange tubing not to contact
cabinet, compressor, shroud and barrier.
Water tank full
Check and pour if the water tank is full.
Water level sensor
Check operation. Drain water if full. Replace if tank is empty and
code is set.
Water depth is overloaded in
chassis
Check and drain the water in the chassis by opening the drainage
hose on the chassis.
Water depth sensing structure Check and replace, or realign if the structure failed.
Air filter
Clean or replace if restricted.
Air discharge pipe
Realign and assemble if the installation of the air discharging pipe
failed. Replace if damaged.
Unit undersized
Determine if the unit is properly sized for the area to be cooled or
heated.
Condenser and Evaporator
Clean or replace if restricted.
Circulation in condensing
water
Check whether water damaged the motor or if the water hose is
blocked.
Fan motor
Check the fan capacitor and replace if not /-10% of
manufacturer’s rating.
Air flow
Clean or remove if any barrier is found to block the inlet/outlet
airflow of the unit.
Less refrigerant
Check the tubes for leakage points. Recycle the refrigerant,
correct the leakage points and recharge.
Capillary tube
Regulate the capillary tube flow and make the evaporating
temperature appropriate if the evaporator is frosted over. Replace
if blocked. Repair joint if leaking.
Compressor
The inlet and outlet valve of the compressor is damaged,
making the low pressure connected with the high pressure.
The refrigerating system cannot produce high pressure and low
pressure. Replace the compressor after checking for this.
No power
Check the voltage. Call an electrician if not within the limit.
Wiring
Check the terminals. Repair and correct if loose.
Temperature setting
Check and adjust the temperature setting.
Compressor
Check and replace if the compressor, the overload protector or
wiring is broken.
Overheat fuse failure
Check and replace if the fuse is damaged.
Main PCB
Check the voltage of the main PCB. Replace the main PCB when
the unit fails in heating mode.
Power supply
The input power supply voltage is too low. Call an electrician if not
within limits.
Main PCB
Check and replace the main PCB if the compressor relay on the
PCB is shorted or damaged.
Room temperature
When the room temperature is too high, the compressor will
protect.
Содержание SRCOOL33K
Страница 4: ...4 2 Unit Dimensions 78 4 in 1991 mm 42 7 in 1085 mm 23 6 in 599 mm...
Страница 7: ...7 5 PCB and Wiring Diagrams 5 1 Circuit Diagram UPPER FAN MOTOR LOWER FAN MOTOR...
Страница 10: ...10 5 PCB and Wiring Diagrams 5 2 1 3 Power PCBA Gerber Layout...
Страница 14: ...14 5 PCB and Wiring Diagrams 5 2 3 2 Translator PCBA Gerber Layout...
Страница 39: ...39 2 Dimensiones de la Unidad 1991 mm 78 4 1085 mm 42 7 599 mm 23 6...
Страница 45: ...45 5 Diagramas del Cableado y PCB 5 2 1 3 Diagrama PCBA Gerber de Energ a...
Страница 49: ...49 5 Diagramas del Cableado y PCB 5 2 3 2 Diagrama del Traductor PCBA Gerber...
Страница 71: ...71...
Страница 72: ...72 18 06 003 93 3868_RevA 1111 W 35th Street Chicago IL 60609 EE UU www tripplite com support...