7. Installation
AC Input and Output Maximum Current & Power Cable Configuration
Note:
Use copper wire with temperature resistance up to 105°C.
Small-Frame Units (30U) including Battery Module(s)
30kVA
60kVA
90kVA*
Installation Breaker Size Recommended
200A
200A
200A
Max Current (A)
57
114
171
Power and Ground Cable (mm²)
95
95
95
Fixation Torque Force (N·m)
2.26
2.26
2.26
* 90kVA without Battery Modules in Small Frame. Requires external battery installation.
Medium-Frame Units (42U) including Battery Module(s)
30kVA
60kVA
90kVA
Installation Breaker Size Recommended
250A
250A
250A
Max Current (A)
57
114
171
Power and Ground Cable (mm²)
120
120
120
Fixation Torque Force (N·m)
2.26
2.26
2.26
Large Frame (42U) without Battery Modules
30kVA
60kVA
90kVA
120kVA
150kVA
180kVA
210kVA
Installation Breaker Size Recommended
400A
400A
400A
400A
400A
400A
400A
Max Current (A)
57
114
171
228
285
342
399
Power and Ground Cable (mm²)
300
300
300
300
300
300
300
Fixation Torque Force (N·m)
2.26
2.26
2.26
2.26
2.26
2.26
2.26
DC Input Maximum Current and Power Cable Configuration
Small Frame (30U) including Battery Module(s)
Nominal Battery V/-240VDC
30kVA
60kVA
90kVA*
External Battery Breaker Recommended
100A
200A
300A
Power and Ground Cable (mm²)
25
95
150
Fixation Torque Force (N·m)
2.26
2.26
2.26
* 90kVA without Battery Modules in Small Frame. Requires external battery installation.
Medium Frame (42U) including Battery Module(s)
30kVA
60kVA
90kVA
External Battery Breaker Recommended
100A
200A
300A
Power and Ground Cable (mm²)
25
95
150
Fixation Torque Force (N·m)
2.26
2.26
2.26
Large Frame (42U) without Battery Modules
30kVA
60kVA
90kVA
120kVA
150kVA
180kVA
210kVA
External Battery Breaker Recommended
100A
200A
300A
400A
500A
600A
700A
Power and Ground Cable (mm²)
25
95
150
240
120 x 2
150 x 2
240 x 2
Fixation Torque Force (N·m)
2.26
2.26
2.26
2.26
2.26
2.26
2.26