13. Technical Specifications
MODEL
30K
60K
90K
120K
150K
180K
210K
CAPACITY
30kVA/30kW 60kVA/60kW
90kVA/90kW 120kVA/120kW 150kVA/150kW 180kVA/180kW 210kVA/210kW
TOPOLOGY
Voltage and Frequency Independent (VFI) True on-line Double Conversion
INPUT
Voltage
380/400/415V (Ph-Ph), 220/230/240V (Ph-N)
Voltage Range
305 to 477V (100% load) / 208 to 305V (70% load)
Phase
3-phase, neutral and ground
Operating Frequency
50/60 Hz (selectable)
Frequency Range
40 Hz ~ 70 Hz ± 0.1 Hz
Power Factor
>0.99%
THDi
<3%
Inverter Bridge
IGBT technology
OUTPUT
Voltage
380/400/415V (3ph, 4 wire, neutral** reference to bypass neutral)
AC Voltage Regulation
<1% (balanced load)
Frequency
50/60 Hz (selectable)
Frequency Range
40 Hz ~ 70 Hz ± 0.1 Hz
Overload
AC mode
100-110%: 60 min
111-120%: 10 min
121-150%: 1 min
>150%: 200 ms
Battery mode
100-110%: 60 min
111-125%: 10 min
126-150%: 1 min
>150%: 200 ms
Crest Factor
3:1
Harmonic Distortion
<2% (100% linear load); <4% (100% non-linear load)
Output Waveform
Pure sine wave
BYPASS
Automatic Bypass
Standard
Manual Maintenance Bypass
Standard
Transfer Time
0 ms
Default Bypass Voltage Tolerance
+15/-20%
Overload
105 to 110%: 60 min
111 to 125%: 10 min
126 to 150%: 1 min
>150%: 200 ms
BATTERY
Battery Type*
Maintenance-free sealed valve-regulated lead acid (VRLA)
Battery Capacity*
12V 9Ah per battery module
Float Voltage
2.3V/cell
Boost Voltage
2.35V/cell
End of Discharge Voltage
1.67V/cell
Battery Storage Time*
6 months (without recharge, 25°C)
Battery Charger Capacity
8A per power module
ENVIRONMENT
Efficiency (Inverter Mode)
>94%
Efficiency (ECO Mode)
>98%
Operating Temperature
0 to 40°C
Storage Temperature (Excl Battery Module)
-15 to 60°C
* Applies to Small- and Medium-Frame systems with internal battery modules. **The UPS output Neutral must be connected to the Load Neutral at all times.