![Tripp Lite SmartOnline SVX Series Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/tripp-lite/smartonline-svx-series/smartonline-svx-series_owners-manual_1167923030.webp)
30
9. Control Panel
WARNINGS
LCD Display Text
Explanation
Warning ! EPO Active
Emergency Power Off activated
Warning ! Overload Fail
UPS system is heavily overloaded; UPS will transfer to bypass
Warning ! Communication CAN Fail
CAN communication failure
Warning ! Overload
UPS system is overloaded
Warning ! Battery Open
The battery is disconnected
Warning ! Battery Voltage High
Battery voltage is too high
Warning ! Module Unlock
Power Module is not connected
Warning ! Turn On Abnormal
Input voltage/frequency out of tolerance
Warning ! Charge Fail
Battery voltage is <10V per battery in charge
Warning ! EEPROM Fail
EEPROM operation failure
Warning ! Fan Lock
Fan is static or locked
Warning ! Line Phase Error
R-S-T phase sequence error
Warning ! Bypass Phase Error
R-S-T phase sequence error
Warning ! N Loss
Loss of neutral
Warning ! Internal Initial Fail
EEPROM operation failure
Warning ! Comm Syn Signal Fail
Communication synchronization signal failure
Warning ! Comm TRIGO Fail
Communication trigger system failure
Warning ! Parallel Sys Config Wrong
Parallel system has been incorrectly configured/installed
Warning ! Maintenance Bypass
UPS is transferred to bypass
Warning ! Battery Age Alert
The batteries are at the end of their useful life
Warning ! Battery Voltage Low
Battery voltage is too low
Warning ! ID Conflict
Power Module ID address conflict
Table 9.7
PRE-ALARMS
LCD Display Text
Explanation
Pre-Alarm ! Line Voltage Fail
Utility voltage is outside acceptable limits
Pre-Alarm ! Line Voltage Normal
Utility voltage recovered to acceptable range
Pre-Alarm ! Line Frequency Unstable
Utility frequency is outside acceptable limits
Pre-Alarm ! Line Frequency Normal
Utility frequency recovered to acceptable range
Pre-Alarm ! Overload
UPS system is overloaded
Pre-Alarm ! Load Normal
UPS system load within UPS rating capacity
Pre-Alarm ! Load Unbalance
Connected loads unbalanced
Table 9.8