9 – Power Module Status and Replacement
Warning: Only authorized Tripp Lite service technicians with knowledge and operational training of this equipment
should install, repair or remove any system components, including power modules. Only power modules with the same
firmware versions may be placed within the same UPS system frame. Verify power module firmware version before
replacement. Permanent power module removal or addition can only be performed by Tripp Lite authorized service
technicians.
9-1 Power Module Features and Status
Each Power Module features an LED indicator to inform the user of its
status.
LED Indicator Statuses
“ON”—The power module is active and functioning properly.
“FLASHING”—The power module has failed and is offline.
“OFF”—When the locking latch is in “UNLOCKED” ( ) position, the
power module is inactive.
When the locking latch is in “LOCKED” ( ) position and the
main power is on, the power module has failed.
9-2 Preliminary Replacement Checklist
• Before removing a Power Module, ensure that the remaining Power Modules can support the connected load.
• Verify that the Power Module needs service or replacement via its individual LED status indicator.
• Do not attempt to remove Power Modules by yourself. Power Modules weigh 30 kg (66 lb) and require at least two people for proper handling.
• Power Modules can be replaced in any UPS Operating Mode. It is not necessary to power loads off or leave them unprotected.
Note: UPS must
be able to support load without the Power Modules to be replaced. If the UPS cannot handle the load once the Power Module is deactivated, an
overload will occur and the UPS will shut down.
• Replace power modules with same firmware version only.
9-3 Replacement Procedure
To Remove Power Module
1. Remove the bezel cover of the Power Module you wish to
replace. Verify that there is a fault through the individual LED
status and UPS LCD screen.
2. Deactivate the Power Module by turning the spring-activated
knob of the locking latch counter-clockwise until it pops out.
Move the locking latch to “UNLOCKED” ( )
3. Use a screwdriver to remove the screws on either side of the
Power Module (total of 4).
4. With one person on either side of the Power Module, pull out and
lift the module from the UPS frame.
To Replace Power Module:
Verify power module replacement has the same firmware version
(as labeled).
With one person on either side of the repaired or new Power
Module, lift and align the Power Module into the appropriate slot
on the UPS. Slide the Power Module in until it is fully inside the
unit and seated flush with its brackets.
Use a screwdriver to fasten the screws on either side of the Power
Module (total of 4).
Move the locking latch to “LOCKED” ( ) position and turn
clockwise until it pops in. Power Module will activate.
9
Verify that the Power Module is activated via the status LED and
UPS LCD screen before replacing the bezel cover.
1
2
3
4
5
6
7
8
12-212-93-3141.indb 29
12/28/2012 11:17:53 AM
Содержание SmartOnline SU120KX2
Страница 178: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 178 2 0 40 C 17 29 C 60 3 12 212 93 3141 indb 178 12 28 2012 11 21 23 AM...
Страница 193: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 193 7 7 8 MUS 7 4 2 4 MUS 7 9 MUS 12 212 93 3141 indb 193 12 28 2012 11 22 03 AM...
Страница 205: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 1 205 10 10 3 1 1 10 3 1 12 212 93 3141 indb 205 12 28 2012 11 22 35 AM...
Страница 206: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 2 3 4 206 10 10 3 1 2 3 4 12 212 93 3141 indb 206 12 28 2012 11 22 36 AM...
Страница 207: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 5 6 7 207 10 10 3 1 5 6 7 12 212 93 3141 indb 207 12 28 2012 11 22 37 AM...
Страница 208: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 8 9 208 10 10 3 1 8 9 10 4 12 212 93 3141 indb 208 12 28 2012 11 22 37 AM...
Страница 209: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 209 10 10 4 1 MEASURE 2 ESC 12 212 93 3141 indb 209 12 28 2012 11 22 38 AM...
Страница 210: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 210 10 10 5 4 0000 0000 1 2 12 212 93 3141 indb 210 12 28 2012 11 22 39 AM...