8 – Start-Up, Shutdown and Bypass
(continued)
1
2
8-8 Start-Up Procedure (Parallel UPS—MUS)
•
Connect the parallel configuration cable
A
(shipped with each
UPS) to the DB9 parallel configuration port
B
of each UPS
system.
Note: Before starting up the Parallel UPS system, ensure
that the “Parallel ID” is different for each UPS and parallel group
is set to 2. See
Section 10-5-5
for more details.
Refer to
Section 6-8 or 6-9
for the appropriate settings of the
parallel port DIP switches and parallel cable connections.
•
With each UPS system’s external battery cabinet connected, switch
on the external battery cabinet circuit breaker switch of each
battery cabinet.
•
Confirm that the manual bypass breaker
Q3
on each UPS system is
off. Switch on the bypass input circuit breaker switch
Q2
of each
UPS system. After a brief initialization process, the LCD screen
will show “ON AUTO BYPASS” and the “BYPASS” LED will
illuminate.
•
Switch on the main input circuit breaker switch
Q1
of each UPS
system.
•
Press the ON button
A
of one of the UPS systems for 3 seconds
(until you hear a beep), then release the button. The inverter will
activate and synchronize with the bypass source. Press the ON
button for each of the other UPS systems for 3 seconds (until you
hear a beep), then release the button. When the inverter of each
UPS system is operating normally, they will automatically switch
from auto bypass mode to on-line (normal) mode at the same time.
The “BYPASS” LEDs
B
will turn off and the “NORMAL” LEDs
C
will illuminate.
•
Check the output voltage of each UPS system. The phase voltage
deviation between each UPS system should be less than 5V. If the
phase deviation is within the acceptable range, switch on the output
circuit breaker switch
Q4
of each UPS system.
Note: For more
information on checking the output voltage of each UPS system,
see
Section 10-4
.
3
4
5
6
12-212-93-3141.indb 25
12/28/2012 11:17:46 AM
Содержание SmartOnline SU120KX2
Страница 178: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 178 2 0 40 C 17 29 C 60 3 12 212 93 3141 indb 178 12 28 2012 11 21 23 AM...
Страница 193: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 193 7 7 8 MUS 7 4 2 4 MUS 7 9 MUS 12 212 93 3141 indb 193 12 28 2012 11 22 03 AM...
Страница 205: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 1 205 10 10 3 1 1 10 3 1 12 212 93 3141 indb 205 12 28 2012 11 22 35 AM...
Страница 206: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 2 3 4 206 10 10 3 1 2 3 4 12 212 93 3141 indb 206 12 28 2012 11 22 36 AM...
Страница 207: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 5 6 7 207 10 10 3 1 5 6 7 12 212 93 3141 indb 207 12 28 2012 11 22 37 AM...
Страница 208: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 8 9 208 10 10 3 1 8 9 10 4 12 212 93 3141 indb 208 12 28 2012 11 22 37 AM...
Страница 209: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 209 10 10 4 1 MEASURE 2 ESC 12 212 93 3141 indb 209 12 28 2012 11 22 38 AM...
Страница 210: ...1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 210 10 10 5 4 0000 0000 1 2 12 212 93 3141 indb 210 12 28 2012 11 22 39 AM...