4.11 Warning Code
4. Operation
5. Communication
If errors occur in the UPS but it continues to run normally, the LCD screen will show a warning. In the warning screen, the icon will
flash. Up to 3 error codes may be displayed, each code indicating one error.
Warning code Warning event
01
Battery disconnected
02
IP neutral loss
04
IP phase abnormal
05
Bypass phase abnormal
07
Over charge
08
Low battery
09
Overload
0A
Fan failure
0B
EPO enable
0D
Over-temperature
0E
Charger failure
Warning code Warning event
10
L1 IP fuse damaged
11
L2 IP fuse damaged
12
L3 IP fuse damaged
21
Line situations are different in parallel system
22
Bypass situations are different in parallel system
33
Locked in bypass after overload 3 times in
30 minutes
34
Converter current imbalanced
35
Battery fuse damaged
3A
Cover of maintenance switch is open
3C
Utility power imbalanced
3D
Bypass unstable
5.1 RS-232 Port
The RS-232 port is built into the UPS system’s rear panel to provide communication between the UPS and computer. Use Tripp Lite’s
free PowerAlert
®
power management software (available for download at www.tripplite.com/poweralert) to:
1. Define shutdown delay time (battery shutdown).
2. Perform unmanned shutdown and restart of UPS and computer in the event of an extended utility failure.
5.2 SMART Slot
Install an optional WEBCARDLX in this slot to remotely monitor and control the UPS via a network. The RELAYCARDSV may also be
inserted in this slot to provide dry contact communication functionality. Refer to the WEBCARDLX and RELAYCARDSV manuals for further
details.
Note:
Only one card may be used at a time.
5.3 EPO Connector
The EPO is included as standard for site safety. Keep pins 1 and 2 closed for normal UPS operation. To enable EPO function, open
contact between pins 1 and 2.
Содержание SmartOnline AG-0149 Series
Страница 99: ...99 1 Tripp Lite SmartOnline SVTKX 3 10 20 30 SVT20KX SVT30KX ECO SNMP SmartOnline SVTKX...
Страница 101: ...101 2 2 4 2 5 2 6 2 7 TN 3...
Страница 108: ...108 4 H M S 3 9 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO 0 25 26 50 51 75 76 100 VAC VDC Hz...
Страница 109: ...109 4 4 3 2 4 4 4 4 4 1 1 ON 2 2 ON 0 5 3 4 4 2 1 ON 2 ON Standby ON 0 5 3 4 4 3 1 2 3 4 80 5 4 4 4 1 2 10...
Страница 116: ...116 4 10 11 12 2 N L 3 DIS ATO CHE 1 Enter CHE 2 Enter CHE 13 2 Add Sub 3 0 9 9 0 14 2 Add Sub 3 0 9 9 0...
Страница 118: ...118 4 4 8 1 3 An bn Cn 3 Ab bC CA 2 PAR 2 3 001 002 003...
Страница 119: ...119 4 ECO ECO...
Страница 120: ...120 4 Freq Converter CF 50 60 4...
Страница 121: ...121 4 2 Freq Converter Test 0 5 3 4 11 123...
Страница 124: ...124 6 EPO EPO OFF EPO 43 14 Tripp Lite 10 Tripp Lite Tripp Lite Tripp Lite 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Страница 125: ...125 7 7 1 7 24 3 7 2 BUS 7 3 Tripp Lite SVTKX 1 0 40 C 2 25 C 3 24 7 4 TrippLite...