20
4. Operation
10: Reserved
Interface
Setting
Reserved for future options.
11: Reserved
Interface
Setting
Reserved for future options.
12: Neutral loss detection
Interface
Setting
Parameter 2:
N.L:
Indicates neutral loss detection function.
Parameter 3:
DIS:
Disable the neutral loss detection function. The UPS will not detect the neutral loss.
ATO:
The UPS will automatically detect if the neutral is lost. If neutral loss is detected, an alarm
will sound. If the UPS is turned on, it will transfer to battery mode. When neutral is restored
and detected, the alarm will be muted automatically and the UPS will go back to Normal mode
automatically.
CHE:
The UPS will automatically detect the neutral loss. If neutral loss is detected, an alarm will
sound. If the UPS is turned on, it will transfer to battery mode. When neutral is restored, the alarm
will NOT be muted automatically and the UPS will NOT go back to normal mode automatically.
You must mute the alarm and put the UPS back to Normal mode manually using these steps:
1) Enter this menu and press the “Enter” key to make the “CHE” flash. 2) Press the “Enter” key
again to activate the neutral detection (check). If neutral is detected, the alarm will be muted and
the UPS will go back to normal mode. If neutral is not detected, the UPS will continue sounding
an alarm and stay on the latest status until the neutral is properly detected at the next manual
checking operation.
CHE is the default setting.
13: Battery voltage calibration
Interface
Setting
Parameter 2:
Select
Add
or
Sub
function to adjust battery voltage to actual figure.
Parameter 3:
The voltage range is from 0V to 9.9V. The default value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2:
Choose
Add
or
Sub
to adjust charger voltage
Parameter 3:
The voltage range is from 0V to 9.9V. The default value is 0V.
Notes:
• Battery disconnect should be performed by qualified service personnel only.
• Before making voltage adjustments, be sure to first disconnect all batteries to get the accurate charger voltage.
• Any modifications must be within range of the batteries’ specifications.
Содержание SmartOnline AG-0149 Series
Страница 99: ...99 1 Tripp Lite SmartOnline SVTKX 3 10 20 30 SVT20KX SVT30KX ECO SNMP SmartOnline SVTKX...
Страница 101: ...101 2 2 4 2 5 2 6 2 7 TN 3...
Страница 108: ...108 4 H M S 3 9 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO 0 25 26 50 51 75 76 100 VAC VDC Hz...
Страница 109: ...109 4 4 3 2 4 4 4 4 4 1 1 ON 2 2 ON 0 5 3 4 4 2 1 ON 2 ON Standby ON 0 5 3 4 4 3 1 2 3 4 80 5 4 4 4 1 2 10...
Страница 116: ...116 4 10 11 12 2 N L 3 DIS ATO CHE 1 Enter CHE 2 Enter CHE 13 2 Add Sub 3 0 9 9 0 14 2 Add Sub 3 0 9 9 0...
Страница 118: ...118 4 4 8 1 3 An bn Cn 3 Ab bC CA 2 PAR 2 3 001 002 003...
Страница 119: ...119 4 ECO ECO...
Страница 120: ...120 4 Freq Converter CF 50 60 4...
Страница 121: ...121 4 2 Freq Converter Test 0 5 3 4 11 123...
Страница 124: ...124 6 EPO EPO OFF EPO 43 14 Tripp Lite 10 Tripp Lite Tripp Lite Tripp Lite 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Страница 125: ...125 7 7 1 7 24 3 7 2 BUS 7 3 Tripp Lite SVTKX 1 0 40 C 2 25 C 3 24 7 4 TrippLite...