background image

20 millisecond automatic transfer between line and battery power supports UPS protection during blackouts and voltage fluctuations for

equipment compatible with a one cycle transfer time

Double Boost inverter output supports momentary startup loads up to 200% of the continuous rating for up to 10 seconds (see specification

chart)

OverPower inverter output supports longer duration overloads to 150% for 1-60 minutes under ideal battery and temperature conditions.

3 stage, 30 amp battery charger with adjustable settings for wet/gel battery types offers fast, reliable battery recharging

3 position operating mode switch supports "AUTO" mode to enable automatic transfer between DC and AC modes, CHARGE-ONLY to

maintain a full battery charge when AC is present without auto transfer and SYSTEM OFF settings

Set of six front panel LEDs display AC/DC operational modes, overload status, DC voltage level, shutdown status and system fault status

Set of 4 configuration dipswitches support wet/gel battery charging profiles, adjustable 259/264V high voltage auto transfer during

overvoltages and selectable 144/163/182/201V AC low voltage auto transfer during brownouts

Set of 4 additional configuration dip switches support 4 levels of charger limiting relative to output load size

Resettable 10A charger AC input breaker and resettable 15A AC output breaker and automatic 2 speed cooling fan protect the inverter from

load and temperature related failures

Automatic overload and thermal shutoff safely turns off inverter as excessive loads or overheating conditions develop

Front panel remote control connector enables remote off/on switching (requires APSRM4 switch accessory)

Specifications

OVERVIEW

Intended
Application

Emergency Home Power

OUTPUT

Frequency
compatibility

50 Hz

Output watts

3600

Continuous output
capacity (watts)

3600

Peak output
capacity (watts)

7200

Output nominal
voltage

230V

Output voltage
regulation

LINE POWER (AC): Maintains 230V nominal sine wave output from line power source. INVERTER POWER (AC):
Maintains PWM sine wave output voltage of 230 VAC (+/-5%).

Output frequency
regulation

50 Hz (+/- 0.3 Hz)

Overload
protection

Includes 12A input breaker dedicated to the charging system and 20A output breaker for AC output loads.

Outlet quantity /
type

Hardwire

INPUT

Recommended
Electrical Service

DC INPUT: Requires 36VDC input source capable of delivering 114A for the required duration (when used at full
continuous capacity - DC requirements increase during OverPower and DoubleBoost operation). For automotive
applications, professional hardwire installation with 300A minimum battery system fusing is recommended.

Maximum input
amps / watts

DC INPUT: Full continuous load - 114A at 36VDC. AC INPUT: 26 amps at 230VAC with full inverter and charger load
(10.4A max charger-only / combined input load to support charger and AC output is automatically controllable to
66%-33%-0% based on AC output loading using the charger limiting set points - see manual for setting instructions)

Input connection
type

DC INPUT: Set of DC bolt-down terminals. AC INPUT: Hardwire via built in junction box with cover plate

Voltage
compatibility (VAC)

230

Отзывы: